Function library
Function blocks
9.2.48
Oscilloscope function (OSC)
9-172
L
EDSVS9332S-D11 EN 3.0
Functional description
Function
Code
Selection
Description
OSC mode
Controls the measurement in the controller
C0730
1
•
Starts the recording of the measured values
C0730
0
•
Cancels a running measurement
OSC status
Displays five different operating states
C0731
1
•
Measurement completed
– The memory of the measured values is completely filled with measured data. The
measured values can be accessed via the PC.
2
•
Measurement active
– A measurement was started with C0730 = 1. The FB is waiting for a valid trigger
event.
3
•
Trigger detected
– The FB has detected a valid trigger event. Depending on the trigger delay the
saving of the measured data is not yet completed. It is automatically completed
with the entry of the last memory unit.
4
•
Measurement cancelled
– Cancel of a running recording of the measured values (C0730 = 0). The memory of
the measured values is filled with the data that has just been measured. The data
can be accessed via the PC.
5
•
Read data memory
– The measured data memory is being read at the moment. No settings are possible
in this operating state.
Configuration
OSC channel
1 ... 4
C0732/1
to
C0732/4
•
Links the measuring channels of the FB with the signals of the process environment
– The four measuring channels can be assigned with any analog signal. Enter the
corresponding signal number into C0732/1 ... C0732/4.
– Always start linking with channel 1, then channel 2 and so on. Unused channels
are automatically assigned with signal FIXED 0%.
Configuration
OSC trigger
C0733/1
Links the digital trigger input with a digital signal in the process environment.
– The trigger input can be assigned with any digital signal. Enter the corresponding
signal number into C0733/1.
Trigger source
Defines the trigger source
C0734
1
Source is one of the four measuring channels (C0734/1 ... C0734/4
C0734
0
Source is the digital trigger input (C0733/1)
Trigger level
C0735
-32767 ... 32767
•
Defines the trigger level which activates the triggering when the threshold is
exceeded.
– The trigger level is only monitored when the triggering is done on one of the four
channels.
– The trigger level is not effective with digital triggering.
Trigger edge
Defines the trigger edge which activates the triggering.
•
Triggering on an analog input channel
– With a LOW-HIGH trigger edge the analog trigger signal must exceed a defined
trigger level to activate the triggering.
– With a HIGH-LOW trigger edge the analog trigger signal must fall below a defined
trigger level to activate the triggering.
•
Triggering on a digital trigger input
– With a LOW-HIGH trigger edge the digital trigger signal must change from LOW to
HIGH to activate the triggering.
– With a HIGH-LOW trigger edge the digital trigger signal must change from HIGH to
LOW to activate the triggering.
Fig. 9-125 shows the triggering of an analog signal with a positive edge.
C0736
1
–
HIGH-LOW trigger edge
C0736
0
LOW-HIGH trigger edge
Summary of Contents for EVS 9300 series
Page 1: ...L System Manual EDSVS9332S 31S Global Drive 9300 servo inverter 31S...
Page 28: ...Contents ii L EDSVS9332S B EN 3 0...
Page 38: ...Technical data 3 6 Dimensions 3 10 L EDSVS9332S B EN 3 0...
Page 90: ...Contents ii L EDSVS9332S C EN 3 0...
Page 108: ...During operation Operating notes 6 6 l EDSVS9332S C EN 3 0...
Page 114: ...Contents iv L EDSVS9332S D11 EN 3 0...
Page 378: ...Contents ii L EDSVS9332S D12 EN 3 0...
Page 452: ...Contents ii L EDSVS9332S E EN 3 0...
Page 466: ...Contents ii L EDSVS9332S K EN 3 0...
Page 467: ...Selection help 11 1 l EDSVS9332S K EN 3 0 Part K 11 Selection help 11 1 See folder Planning...
Page 468: ...Selection help 11 2 l EDSVS9332S K EN 3 0...
Page 485: ...Contents i L EDSVS9332S L EN 3 0 13 Signal flow diagrams 13 1...
Page 486: ...Contents ii L EDSVS9332S L EN 3 0...
Page 488: ...Signal flow charts 13 2 L EDSVS9332S L EN 3 0...
Page 491: ...Contents i L EDSVS9332S M EN 3 0 14 Glossary 14 1 14 1 Index 14 3...
Page 492: ...Contents ii L EDSVS9332S M EN 3 0...