Function library
Code table
9-264
l
EDSVS9332S-D12 EN 3.0
Code
Important
Possible settings
No.
Selection
Lenze
LCD
C0265 MPOT1 INIT
0
0
1
2
Value during mains failure
lower limit of C0261
0 %
MPOT1
Initialisation. Value which is accepted during
mains switching and activated motor
potentiometer.
[C0267]
→
Selection list 2 Digital inputs motor potentiometers
1 UP
1000
FIXED0
g
p
p
C0267/1: Mpot-UP
C0267/2 MPOT D
2 DOWN
1000
FIXED0
C0267/2: MPOT-Down
[C0268] MPOT1-INACT
1000
FIXED0
→
Selection list 2
MPOT1
Input signal configuration
C0269
1 (C0267/1)
2 (C0267/2)
3 (C0268)
C0291 SSC override
0
0
{1 rpm}
16000
SSC override frequency
C0292 SSC IM SET
0.00
0.00
{0.01 A}
500.00
SSC Im setpoint
Motor current. Set approx. 1.0 to 1.1- fold rated
motor current for sensorless control. Setpoint
C0293 SSC dynamic
0.00
{0.01 %}
199.00
SSC Dynamic constant
C0294 VP FRQ CTRL
→
0.0
{0.1 }
99.9
SSC V
p
frequency controller
Proportional gain of frequency controller
→
depending on C0086
C0295 TN FRQ CTRL
→
2
{1 ms}
20000
Tn frequency controller
Adjustment time frequency controller
→
depending on C0086
C0296 DYNAMIC CONST
100
0
{0.1 }
32767
Dynamic constant
C0325 VP2 ADAPT
1.0
0.1
{0.1 }
500.0
PCTRL
Process controller adaptation gain (V
p2
)
C0326 VP3 ADAPT
1.0
0.1
{0.1 }
500.0
PCTRL
Process controller adaptation gain (V
p3
)
C0327 SET2 ADAPT
100.00 0.00
{0.01 %}
100.00
PCTRL
Set speed threshold nset2 of the process
controller adaptation (condition:
C0327 > C0328)
C0328 SET1 ADAPT
0.00
0.00
{0.01 %}
100.00
PCTRL
Set speed threshold nset1 of the process
controller adaptation (condition:
C0328 < C0327)
C0329 ADAPT ON/OFF
0
0
1
2
3
No process controller adaptation
External via input
Adaptation via setpoint
Adaptation via control difference
PCTRL
Activate process controller adaptation
C0332 PCTRL TIR
0.000
0.000
{0.001 s}
999.900
PCTRL
Acceleration time Tir
Refers to setpoint change 0...100 %
C0333 PCTRL TIF
0.000
0.000
{0.001 s}
999.900
PCTRL
Deceleration time Tif
Refers to setpoint change 0...100 %
C0336 ACT VP
0.0
{0.1 }
500.0
PCTRL
Current Vp
C0337 BI/UNIPOLAR
0
0
1
Bipolar
Unipolar
PCTRL
Bipolar/unipolar range of action
C0338 ARIT1 FUNCT
1
0
1
2
3
4
5
OUT = IN1
OUT = IN1 + IN2
OUT = IN1 - IN2
OUT = IN1 * IN2
OUT = IN1 / IN2
OUT = IN1/(100% - IN2)
ARIT1
Function selection
Summary of Contents for EVS 9300 series
Page 1: ...L System Manual EDSVS9332S 31S Global Drive 9300 servo inverter 31S...
Page 28: ...Contents ii L EDSVS9332S B EN 3 0...
Page 38: ...Technical data 3 6 Dimensions 3 10 L EDSVS9332S B EN 3 0...
Page 90: ...Contents ii L EDSVS9332S C EN 3 0...
Page 108: ...During operation Operating notes 6 6 l EDSVS9332S C EN 3 0...
Page 114: ...Contents iv L EDSVS9332S D11 EN 3 0...
Page 378: ...Contents ii L EDSVS9332S D12 EN 3 0...
Page 452: ...Contents ii L EDSVS9332S E EN 3 0...
Page 466: ...Contents ii L EDSVS9332S K EN 3 0...
Page 467: ...Selection help 11 1 l EDSVS9332S K EN 3 0 Part K 11 Selection help 11 1 See folder Planning...
Page 468: ...Selection help 11 2 l EDSVS9332S K EN 3 0...
Page 485: ...Contents i L EDSVS9332S L EN 3 0 13 Signal flow diagrams 13 1...
Page 486: ...Contents ii L EDSVS9332S L EN 3 0...
Page 488: ...Signal flow charts 13 2 L EDSVS9332S L EN 3 0...
Page 491: ...Contents i L EDSVS9332S M EN 3 0 14 Glossary 14 1 14 1 Index 14 3...
Page 492: ...Contents ii L EDSVS9332S M EN 3 0...