Function library
Function blocks
9.2.27
Digital frequency ramp function generator (DFRFG)
9-108
L
EDSVS9332S-D11 EN 3.0
9.2.27.6
Start via touch probe initiator (terminal X5/ E5)
Stop!
In the default setting the terminal X5/E5 is assigned to another function.
Function
z
Set C0757 = 1.
z
The function is activated by
simultaneously
setting the inputs:
– DFRFG-QSP and DFRFG-RESET = HIGH.
z
Starting procedure:
– Signals at DFRFG-QSP and DFRFG-RESET = LOW.
– Otherwise touch probe signals are ignored.
z
A LOW-HIGH edge at terminal X5/E5 starts the process:
t
D
FRFG-RESET
D
FRFG-QSP
Touch-Probe X5/E5
D
FRFG-OUT
D
FRFG-IN
Fig. 9-70
Start via touch probe initiator (terminal X5/E5)
Summary of Contents for EVS 9300 series
Page 1: ...L System Manual EDSVS9332S 31S Global Drive 9300 servo inverter 31S...
Page 28: ...Contents ii L EDSVS9332S B EN 3 0...
Page 38: ...Technical data 3 6 Dimensions 3 10 L EDSVS9332S B EN 3 0...
Page 90: ...Contents ii L EDSVS9332S C EN 3 0...
Page 108: ...During operation Operating notes 6 6 l EDSVS9332S C EN 3 0...
Page 114: ...Contents iv L EDSVS9332S D11 EN 3 0...
Page 378: ...Contents ii L EDSVS9332S D12 EN 3 0...
Page 452: ...Contents ii L EDSVS9332S E EN 3 0...
Page 466: ...Contents ii L EDSVS9332S K EN 3 0...
Page 467: ...Selection help 11 1 l EDSVS9332S K EN 3 0 Part K 11 Selection help 11 1 See folder Planning...
Page 468: ...Selection help 11 2 l EDSVS9332S K EN 3 0...
Page 485: ...Contents i L EDSVS9332S L EN 3 0 13 Signal flow diagrams 13 1...
Page 486: ...Contents ii L EDSVS9332S L EN 3 0...
Page 488: ...Signal flow charts 13 2 L EDSVS9332S L EN 3 0...
Page 491: ...Contents i L EDSVS9332S M EN 3 0 14 Glossary 14 1 14 1 Index 14 3...
Page 492: ...Contents ii L EDSVS9332S M EN 3 0...