Commissioning
5.1
Initial switch-on
5-2
L
EDSVS9332S-C EN 3.0
5.1.1
Switch-on sequence
1. X5/28 (controller enable) must be open (LOW).
2. X5/E4 to HIGH signal (+13 V ... +30 V)
3. Switch on mains:
– The controller is ready for operation after approx. 0.5 s (2 s for drives with sin/cos encoders
with serial interface).
4. Adapt controller to the operating conditions under C0173:
– If the controllers are not adapted, their lives are reduced.
C0173
Mains voltage
upper switch-off threshold
Operation
0
< 400 V
1 (default setting)
400 V
770 V
with or without braking unit
2
400 V < U
mains
≤
460 V
770 V
with or without braking unit
3
480 V
without
braking unit
4
480 V
800 V
with
braking unit
Tip!
For applications with active loads (e. g. hoists) the code C0172* must be set to C0172 = 0 [Volt] in
order to generate an overvoltage message (OU).
As long as the overvoltage message (OU) is applied
z
the pulse inhibit is set and
z
the drive is torqueless.
The controller inhibit is evaluated by the ”holding brake (BRK)” (see chapter in the corresponding
System Manual 9300).
*) C0172 = ”OV reduce - threshold for activating the braking torque reduction before OU message”
5. Enter motor data:
– For drives with a Lenze motor: Select motor under C0086.
– For drives with other motors: See chapter 5.2.
6. Select feedback system:
– Drives with resolver: no change required.
– Drives with other feedback systems:
Select feedback system under C0025,
set encoder voltage with C0421
(menu: ”Motor / feedb.”, submenu: ”Feedback” or
menu: ”Motor/feedback system”, submenu: ”feedback systems”)
– With sensorless control (SSC): C0025 = 1. Do not use this control for new drive tasks.
7. When the digital terminals X5 are supplied with internal voltage:
– Assign output X5/A1 with ”FIXED1”. Approx. 24 V are then output on terminal X5/A1.
8. When the analog terminals X6 are supplied with internal voltage:
– Assign output X6/63 (FB AOUT) with ”FIXED100% ”. 10 V are then output on terminal X6/63.
Summary of Contents for EVS 9300 series
Page 1: ...L System Manual EDSVS9332S 31S Global Drive 9300 servo inverter 31S...
Page 28: ...Contents ii L EDSVS9332S B EN 3 0...
Page 38: ...Technical data 3 6 Dimensions 3 10 L EDSVS9332S B EN 3 0...
Page 90: ...Contents ii L EDSVS9332S C EN 3 0...
Page 108: ...During operation Operating notes 6 6 l EDSVS9332S C EN 3 0...
Page 114: ...Contents iv L EDSVS9332S D11 EN 3 0...
Page 378: ...Contents ii L EDSVS9332S D12 EN 3 0...
Page 452: ...Contents ii L EDSVS9332S E EN 3 0...
Page 466: ...Contents ii L EDSVS9332S K EN 3 0...
Page 467: ...Selection help 11 1 l EDSVS9332S K EN 3 0 Part K 11 Selection help 11 1 See folder Planning...
Page 468: ...Selection help 11 2 l EDSVS9332S K EN 3 0...
Page 485: ...Contents i L EDSVS9332S L EN 3 0 13 Signal flow diagrams 13 1...
Page 486: ...Contents ii L EDSVS9332S L EN 3 0...
Page 488: ...Signal flow charts 13 2 L EDSVS9332S L EN 3 0...
Page 491: ...Contents i L EDSVS9332S M EN 3 0 14 Glossary 14 1 14 1 Index 14 3...
Page 492: ...Contents ii L EDSVS9332S M EN 3 0...