Technical data
3.3
Rated data
3-4
L
EDSVS9332S-B EN 3.0
3.3
Rated data
3.3.1
Types 9321 to 9325
Type
EVS9321-ES
EVS9322-ES
EVS9323-ES
EVS9324-ES
EVS9325-ES
Order No.
EVS9321-ES
EVS9322-ES
EVS9323-ES
EVS9324-ES
EVS9325-ES
Type
EVS9321-CS
EVS9322-CS
EVS9323-CS
EVS9324-CS
EVS9325-CS
Order No.
EVS9321-CS
EVS9322-CS
EVS9323-CS
EVS9324-CS
EVS9325-CS
Mains voltage
U
r
[V]
320 V - 0 %
≤
U
r
≤
528 V + 0 % ; 45 Hz - 0 % ... 65 Hz + 0 %
Alternative DC supply
U
G
[V]
460 V - 0 %
≤
U
G
≤
740 V + 0 %
Mains current with mains filter
I
r
[A]
1.5
2.1
2.5
3.5
3.9
5.5
7.0
-
12.0
16.8
Data for the operation on a mains: 3 AC/400 V / 50 Hz/60 Hz
Motor power (4-pole ASM)
P
r
[kW]
0.37
0.75
1.5
3.0
5.5
Motor power (4 pole ASM)
P
r
[hp]
0.5
1.0
2.0
4.0
7.5
Output power U, V, W (8 kHz*)
S
r8
[kVA]
1.0
1.7
2.7
4.8
9.0
Output power +U
G
, -U
G
2)
P
DC
[kW]
2.0
0.75
2.2
0.75
0
Output current (8 kHz*)
I
r8
[A]
1.5
2.5
3.9
7.0
13.0
Output current (16 kHz*)
I
r16
[A]
1.1
1.8
2.9
5.2
9.7
Max. output current (8 kHz*)
1)
I
max8
[A]
2.3
3.8
5.9
10.5
19.5
Max. output current (16 kHz*)
1)
I
max16
[A]
1.7
2.7
4.4
7.8
14.6
Max. standstill current (8 kHz*)
I
08
[A]
2.3
3.8
5.9
10.5
19.5
Max. standstill current (16 kHz*)
I
016
[A]
1.7
2.7
4.4
7.8
14.6
Data for the operation on a mains: 3 AC/480 V / 50 Hz/60 Hz
Motor power (4-pole ASM)
P
r
[kW]
0.37
0.75
1.5
3.0
5.5
Motor power (4 pole ASM)
P
r
[hp]
0.5
1.0
2.0
4.0
7.5
Output power U, V, W (8 kHz*)
S
r8
[kVA]
1.2
2.1
3.2
5.8
10.8
Output power +U
G
, -U
G
2)
P
DC
[kW]
2.0
0.75
2.2
0.75
0
Output current (8 kHz*)
I
r8
[A]
1.5
2.5
3.9
7.0
13.0
Output current (16 kHz*)
I
r16
[A]
1.1
1.8
2.9
5.2
9.7
Max. output current (8 kHz*)
1)
I
max8
[A]
2.3
3.8
5.9
10.5
19.5
Max. output current (16 kHz*)
1)
I
max16
[A]
1.7
2.7
4.4
7.8
14.6
Max. standstill current (8 kHz*)
I
08
[A]
2.3
3.8
5.9
10.5
19.5
Max. standstill current (16 kHz*)
I
016
[A]
1.7
2.7
4.4
7.8
14.6
Motor voltage
U
M
[V]
0 - 3
×
U
Mains
Power loss (operation with I
rx
)
P
loss
[W]
100
110
140
200
260
Weight
m [kg]
3.5
3.5
5.0
5.0
7.5
1)
The currents apply to a periodical load cycle with 1 minute overcurrent with the current mentioned here and
2 minutes base load with 75% I
rx
2)
When operated under rated load, the controller can supply this power additionally.
*
Switching frequency of the inverter (C0018)
Summary of Contents for EVS 9300 series
Page 1: ...L System Manual EDSVS9332S 31S Global Drive 9300 servo inverter 31S...
Page 28: ...Contents ii L EDSVS9332S B EN 3 0...
Page 38: ...Technical data 3 6 Dimensions 3 10 L EDSVS9332S B EN 3 0...
Page 90: ...Contents ii L EDSVS9332S C EN 3 0...
Page 108: ...During operation Operating notes 6 6 l EDSVS9332S C EN 3 0...
Page 114: ...Contents iv L EDSVS9332S D11 EN 3 0...
Page 378: ...Contents ii L EDSVS9332S D12 EN 3 0...
Page 452: ...Contents ii L EDSVS9332S E EN 3 0...
Page 466: ...Contents ii L EDSVS9332S K EN 3 0...
Page 467: ...Selection help 11 1 l EDSVS9332S K EN 3 0 Part K 11 Selection help 11 1 See folder Planning...
Page 468: ...Selection help 11 2 l EDSVS9332S K EN 3 0...
Page 485: ...Contents i L EDSVS9332S L EN 3 0 13 Signal flow diagrams 13 1...
Page 486: ...Contents ii L EDSVS9332S L EN 3 0...
Page 488: ...Signal flow charts 13 2 L EDSVS9332S L EN 3 0...
Page 491: ...Contents i L EDSVS9332S M EN 3 0 14 Glossary 14 1 14 1 Index 14 3...
Page 492: ...Contents ii L EDSVS9332S M EN 3 0...