![Larsen & Toubro C*2000 Series User Manual Download Page 99](http://html1.mh-extra.com/html/larsen-and-toubro/c-2000-series/c-2000-series_user-manual_676507099.webp)
Chapter 7 Basic Functions
7-18
Cx2000 AC Drive
User V/F pattern operation
Group
Code Item
Set value Range
Initial Unit
Function group 1
F30
V/F pattern
2
0 ~ 2
0
F31
User V/F frequency 1
-
0.00~ 400.00 12.50
Hz
~
~
F38
User V/F voltage 4
-
0 ~ 100
100
%
Set F30 to 2 (user V/F).
User can adjust the Volt/Frequency ratio according to V/F pattern of specialized motors and load
characteristics.
Caution
In case of using a standard induction motor, if this value is set much higher than linear V/F pattern,
it could result in torque shortage or motor overheating due to over-energizing.
When User V/F curve is active, F28 - [Torque Boost in forward direction] and F29 - [Torque Boost
in reverse direction] are deactivated.
Output voltage adjustment
Group
Code Item
Set value
Range
Initial Unit
Function group 1
F39
Output voltage adjustment
-
40 ~ 110
100
%
This function is used to adjust the output voltage of the inverter. This is useful when the raged voltage
of the motor is different from the input voltage of the inverter.
Freq .
V oltage
S tart
freq.
F 31
F 33
F 35
F37
B ase
freq .
F 32
F 34
F 36
F 38
100%
Linear
V/ F
Freq.
V oltage
B ase freq.
100%
70%
100
%
S etting
70
%
S etting
Summary of Contents for C*2000 Series