Chapter 13 Product specifications and options
13-1
Cx2000 AC Drive
13 Product specifications and options
13.1 Basic specifications
Input and output specifications: single-phase input voltage (230V)
LTVF –C1■■■■BAA
0001
0002
0003
0005
0008
0011
Applicable
motor
[HP]
1/8
1/4
1/2
1
2
3
[kW]
0.1
0.2
0.4
0.75
1.5
2.2
Output
ratings
Rated capacity [kVA]
2)
0.3
0.5
1.0
1.9
3.0
4.2
Rated current[A]
3)
0.8
1.4
2.5
5.0
8.0
11
Max. output frequency
400 [Hz]
4)
Max. output voltage [V]
Three phase 200 ~ 240V
5)
Input
ratings
Rated voltage [V]
Single phase 200 ~ 240 VAC (+10%, -15%)
Rated frequency
50 ~ 60 [Hz] ( 5%)
Rated current[A]
1.4
2.8
5.5
11
14.1
24
Cooling type
Natural cooling
Forced cooling
Weight of inverter [kg]
0.55
0.55
0.8
1.22
1.42
1.97
Input and output specifications: three-phase input voltage (230V)
LTVF –C2■■■■BAA
0001 0002 0003 0006 0010
0012 0018 0030
0040
Applicable
motor
1)
HD
[HP]
1/8
1/4
1/2
1
2
3
5
7.5
10
[kW]
0.1
0.2
0.4
0.75
1.5
2.2
3.7
5.5
7.5
ND
[HP]
1/4
1/2
1
1.5
3
4
5.4
10
15
[kW]
0.2
0.4
0.75
1.1
2.2
3.0
4.0
7.5
11.0
Output
ratings
Rated capacity
[kVA]2)
HD
0.3
0.5
1.0
1.9
3.0
4.2
6.1
9.1
12.2
ND
0.4
0.7
1.3
2.4
3.8
5.2
7.6
12.1 16.3
Rated current
[A]
3)
HD
0.8
1.4
2.5
5.0
8.0
11.0
16.0 24.0 32.0
ND
1.1
1.8
3.1
6.3
10.0
12.0
18.0 30.0 40.0
Max. output frequency 400 [Hz]
4)
Max. output voltage [V] Three phase 200 ~ 240V
5)
Input
ratings
Rated voltage [V]
Three phase 200 ~ 240 VAC (+10%, -15%)
Rated current[A]
HD
0.7
1.5
2
5.8
7.5
11
18.9 22.1 28.6
ND
1.1
1.9
3.9
7.3
10.8
13.9
24
28.6 41.2
Rated frequency
50 ~ 60 [Hz] ( 5%)
Cooling type
Natural cooling
Forced cooling
Weight of inverter [kg]
0.55
0.55
0.8
0.8
1.22
1.42
1.97
3.3
3.3
Summary of Contents for C*2000 Series