Chapter 8 Application
8-30
Cx2000 AC Drive
0: continuous operation when cooling fan trip occurs.
-. Operation is not stopped regardless of cooling fan trip.
-.When I55 is set to 18 (cooling fan fault alarm), fault alarm signal can be output using Multi-function
relay.
Caution
If operation is continued after cooling fan trip occurs, Overheat trip may happen and
protective function be activated. It also reduces the life of main components due to rise in
inverter inner temperature.
1: operation stopped at cooling fan fault
-.when cooling fan fault occurs,
message is displayed on the LED and operation is
stopped.
-. If I55 is set to 17(Fault output), fault message is displayed.
8.24 Input voltage set of inverter
Group
Code Item
Set
Value
Setting
Range
Initial
Unit
Function Group 1 F67
Input voltage for 230V inverter
170~240
220
Function Group 1 F68
Input voltage for 415V inverter
320~480
380
F67 set input voltage of 230V level inverter
F68 set input voltage of 415V level inverter
The adjustment of input voltage will influence the voltage level when failure of inverter occurs under low
voltage
8.25 Parameter Initialize / Lock
Parameter initialize
Group
Code Item
Setting Range
Initial
Function group 2
H93
Parameter initialize
0
-
0
1
All groups initialize
2
Drive group initialize
3
Function group 1 initialize
4
Function group 2 initialize
5
I/O group initialize
Select the group to be initialized and perform it in H93 code.