Chapter 5 – Parameter list
5-9
Cx2000 AC Drive
1)
: Set F50 to 1 to display this parameter.
Function group 1
LED
display
Address
for
comm
Parameter
name
Range
Description
Factory
defaults
Adj.
During
run
Page
F55
1237
Overload
warning
time
0.0
~
30.0
[Sec]
This parameter issues an alarm signal when
the current greater than Overload warning
level (F54) flows to the motor for Overload
warning time (F55).
10.0
0
10-2
F56
1238
Overload
trip select
0
~
1
This parameter turns off the inverter output
when motor is overloaded.
1
0
10-3
F57
1239
Overload
trip level
30
~
200[%]
This parameter sets the amount of overload
current.
The value is the percentage of Motor rated
current (H33).
180
0
F58
123A
Overload
trip time
0.0
~
60.0
[Sec]
This parameter turns off the inverter output
when the F57- [Overload trip level] of current
flows to the motor for Overload trip time (F58).
60.0
0
F59
123B
Stall
prevention
select
0
~
7
This parameter stops accelerating during
acceleration, decelerating during constant
speed run and stops decelerating during
deceleration.
0
X
10-3
During
Decel
During
constant run
During
Accel
Bit 2
Bit 1
Bit 0
0
-
-
-
1
-
-
2
-
-
3
-
4
-
-
5
-
6
-
7