Chapter 10 Protective Function
10-8
Cx2000 AC Drive
10.8 DB Resistor Enable Duty setting
Group
Code Parameter
Set Value Range
Initial
Unit
Function
group 2
H75 Enable duty limit
1
0 ~ 1
1
H76 Enable duty
-
0 ~ 30
10
%
Set H75 to 1.
Set %ED (Enable Duty) in H76.
H75: DB resistor ED limit setting
0
Not limit for use of DB resistor
Warning
Take caution when DB resistor is used over its Watt rating.
Fire may result from resistor overheat. When resistor having
heat detection sensor is used, sensor output can be used as
external trip signal in multifunction input.
1
ED is limited as the setting in H76.
H76: set the resistor operating rate (%ED) in one sequence of operation.
Continuous usage rate is Max 15 sec and usage signal is not issued over 15
seconds.
The inverter capacity varies with DB resistor; please refer to Page 13-5.
For 230V inverter, when DC link voltage rises to the value set in F73, the DB resistor is
activated.
Output freq
Relay
Set freq
5s
Run Command