Chapter 7 Basic Functions
7-15
Cx2000 AC Drive
Accel/Decel curve setting
Group
Code Item
Range
Initial
Unit
Function group 1
F 2
Accel pattern
0
Linear curve operation 0
F 3
Decel pattern
1
S curve operation
Function group 2
H17
S-Curve Accel/Decel
start curve
0 ~ 100
40
%
H18
S-Curve Accel/Decel
end curve
40
%
Accel pattern and Decel pattern can be settable at F2, F3 in function group 1.
Linear curve operation: output frequency increases or decreases linearly according to a certain
amount. It is usually used for constant torque.
S curve operation:
This curve allows the motor to accelerate and decelerate smoothly. And it is
applied to application occasion such as lifting load or elevator.
Warning
When S-curve is used, the actual Accel/ Decel time is longer than the value set by user.
O p e ra tin g co m m a n d
F re q .
A cce l tim e
D e ce l tim e
H17 sets the starting ratio between S-curve and Linear in 1/2 of Accel/Decel Ref. Frequency, for smooth
Accel/Decel starting, increase H17 to extend S-curve ratio.
H18 sets the ending ratio between S-curve and Linear in 1/2 of Accel/Decel Ref. Frequency. For smooth
and accurate speed arrival and stopping, increase H18 to extend S-curve ratio.
1/2 of
Accel/Decel
Ref.Freq.
Freq
H17
H17
H18
H18
Accel/Decel
Ref.Freq.
Accel
End
Decel
Start
Decel
End
Summary of Contents for C*2000 Series