![Larsen & Toubro C*2000 Series User Manual Download Page 148](http://html1.mh-extra.com/html/larsen-and-toubro/c-2000-series/c-2000-series_user-manual_676507148.webp)
Chapter 10 Protective Function
10-2
Cx2000 AC Drive
10.2 Overload warning and trip
Overload warning
Group
Code Parameter
Set Value Range
Initial Unit
Function
Group 1
F54
Overload warning level
-
30 ~ 150
150
%
F55
Overload warning time
-
0.0 ~ 30.0 10.0 Sec
I/O Group
I55
Multi-function relay function
select
5
0 ~ 19
17
Set I55 (multi-function relay select) to 5 (Overload: OL)
F54: Set the value as a percent of motor rated current.
F51
F52
60
ETH trip time (sec)
Relay output
F54
t: OL warning time
t
t
Current %
Output current