Chapter 9 Monitoring
9-5
Cx2000 AC Drive
When the fault condition is reset via the STOP/RST key or multi-function terminal, information displayed in
the
nOn
will be moved to H1. In addition, the previous fault info stored in H1 will be automatically moved to
H2. Therefore, the updated fault info will be stored in the H1.
When more than 1 fault occurred at the same time, faults will be stored in one code.
Data in H1~H5 will be initialized during the initialization of parameters. When H6 is set to 1, the data in
H1~H5 will be initialized as well.
After confirmation, the fault will be moved to other codes as follows:
9.4 Analog Output
Group
Code
Name
Set Value
Range
Default
Unit
I/O Group
I50
Analog output item select
-
0 ~ 3
0
I51
Analog output level adjustment
-
10 ~ 200
100
%
Output item and the level from the AM terminal are selectable and adjustable.
I50: The selected item will be output to Analog output terminal (AM).
I50
Analog output item
select
Item corresponding to 10V
200V
400V
0
Output frequency.
Max Frequency (F21)
1
Output current
150% of Inverter rated
current
2
Output voltage
282Vac
564Vac
3
Inverter DC link voltage
410Vdc
820Vdc
I51: If you want to use Analog output value as a gauge input, the value can be adjustable according to
various gauge specifications.
AMT
CM
0 ~ 10Vdc
Operating status at
fault
Fault
types