Chapter 5 – Function list
5-10
Cx2000 AC Drive
F60
123C
Stall
prevention
level
30
~
200[%]
This parameter sets the amount of current to
activate stall prevention function during Accel,
Constant or Decel run.
The set value is the percentage of Motor rated
current (H33).
150
X
10-3
Function group 1
LED
display
Address
for
comm
Parameter
name
Range
Description
Factory
defaults
Adj.
During
run
Page
F61
1)
123D
When
Stall
prevention
during
deceleration,
voltage limit
select
0
~
1
In Stall prevention run during deceleration, if
you want to limit output voltage, select 1
0
X
8-25
F63
123F
Save
up/down
frequency
select
0
~
1
This parameter decides whether to save the
specified frequency during up/down operation.
When 1 is selected, the up/down frequency is
saved in F64.
0
X
8-4
F64
2)
1240
Save
up/down
frequency
-
If „Save up/down frequency‟ is selected at F63,
this parameter saves the frequency before the
inverter stops or decelerated.
0.00
X
8-4
F65
1241
Up-down
Mode select
0
~
2
We can select up-down mode among three
thing
0
X
8-5
0
Increases goal frequency as a
standard of Max. frequency/Min.
frequency
1
Increases step frequency 66 according
to edge input F 66.
2
Available to combine 0 and 1
F66
1242
Up-Down
step
frequency
0.00
~
400.00
[Hz]
In case of choosing F65 as a 1 or 2, it means
increase or decrease of frequency according
to up-down input.
0.00
X
8-5
F67
3)
1243
200V input
voltage
170
~
240[V]
200V inverter input voltage set
220
0
8-30