Chapter 8 Application
8-1
Cx2000 AC Drive
8. Application
8.1 DC brake
Measures to stop motor through DC brake
Group
Code
Item
Set Value
Setting Range
Initial
Unit
Function
Group 1
F 4
Stop mode select
1
0 ~ 3
0
F 8
DC Brake start frequency -
0.10 ~ 60.00
5.00
Hz
F 9
DC Brake wait time
-
0.00 ~ 60.00
0.10
Second
F10
DC Brake voltage
-
0 ~ 200
50
%
F11
DC Brake time
-
0.0 ~ 60.0
1.0
Second
Function group 1: Select 1 (DC brake to stop) in F4 code
F8: Initial frequency for DC brake
F9: Waiting time of inverter before DC brake
F10: Set as per the rated current of motor (based on H33)
F11: The time set shall be the time for work of DC braking voltage
Caution
The over-voltage or overlong time in DC brake will cause overheat or damage of motor.
Setting F10 or F11 to 0 will disable DC brake.
Waiting time of DC brake: When load inertia is large or DC
Brake Start Frequency is high, over current trip may occur. It
can be prevented using F9.
In case of DC brake at high load inertia and frequency,
change the DC brake controller gain according to H37 set
value.
H37
Load inertia ratio
0
Less than 10 times
1
About 10 times
2
More than 10 times
F re q.
O p e ra tio n
C o m m a n d
V o lta g e
C u rre n t
F 8
F9
F11
F10