7.6 Stop mode select
Decel to stop
DC braking to stop
Group
Code Item
Set value Range
Initial Unit
Function group 1
F4
Stop mode selection
1
0 ~ 3
0
Set F4 to 1 (DC braking stop). Refer to page 8-1.
Free run to stop
Group
Code Item
Set value Range
Initial Unit
Function group 1
F4
Stop mode selection
2
0 ~ 3
0
Set F4 to 2 (Free run stop).
When operating command is turned OFF, the inverter turn off the output frequency and voltage,
then the motor stops in the matter of mechanical inertia.
Group
Code Item
Set value Range
Initial Unit
Function group 1
F4
Stop mode selection
0
0 ~ 3
0
Set F4 to 0 (Decel to stop).
Motor decelerates to 0 Hz and stops during the setting time.
O perating com m and
F req .
Decel t i me
R un C om m and
Freq.V oltage