![Larsen & Toubro C*2000 Series User Manual Download Page 126](http://html1.mh-extra.com/html/larsen-and-toubro/c-2000-series/c-2000-series_user-manual_676507126.webp)
Chapter 8 Application
8-23
Cx2000 AC Drive
Selects the self drive in the 2nd switching of drv2 among the followings
drv2 Drive mode 2
0 Operation via Run/Stop key on the Keypad
1
Terminal
operation
FX: Forward run command
RX: Reverse run command
2
FX: Run/Stop command
RX: Forward/Reverse Command
3 Operation via communication RS-485
Selects the self drive in the 2nd switching of Frq2 among the followings
Frq2 Frequency
mode2
0 Digital
Keypad digital frequency mode1
1
Keypad digital frequency mode2
2 Analog
V2 potentiometer: 0~ 5V
3
AI terminal (J1 to V): 0 ~ +10V
4
AI terminal (J1 to I): 0 ~ 20mA
5
V2 potenti AI terminal (J1 to I) set
6
V2 potenti AI terminal (J1 to V) set
7 Operation via communication RS-485
The following is example for switching of drv1 and drv2.
Group
Code
Item
Set Value
Setting
Range
Initial
Unit
Drive group
drv
Drive mode 1
3
0 ~ 3
1
Frq
Frequency mode 1
0
0 ~ 8
0
drv2
Drive mode 2
1
0 ~ 3
1
Frq2
Frequency mode 2
0
0 ~ 7
0
I/O group
I 21
Multi-function input terminal
P5 input terminal
22
0 ~ 27
7
The following figure is drawn when setting is like the above and command frequency is 30 [Hz], F4
[stop method]=0