Chapter 5 – Parameter list
5-5
Cx2000 AC Drive
F 9
1209
DC Brake
wait time
0.00
~
60.00
[sec]
When DC brake frequency is reached,
the inverter holds the output for the
setting time before starting DC brake.
0.10
X
F10
120A
DC brake
Voltage
0
~
200[%]
This parameter sets the amount of DC
voltage applied to a motor.
It is set in percent of Motor rated
current (H33).
50
X
F11
120B
DC brake
Time
0.0
~
60.0
[sec]
The parameter sets the time taken to
apply DC current to a motor while
motor is at a stop.
1.0
X
F12
120C
Brake start
voltage
0
~
200[%]
This parameter sets the amount of DC
voltage before a motor starts to run.
It is set in percent of Motor rated
current (H33).
50
X
8-2
F13
120D
DC brake
start time
0.0
~
60.0
[sec]
DC voltage is applied to the motor for
DC brake start time before motor
accelerates.
0.0
X
1)
: Only displayed when F4 (DC brake stop) is set to 1.
Function group 1
LED
display
Address
for
comm
Parameter
name
Range
Description
Factory
defaults
Adj.
During
run
Page
F14
120E
Time for
magnetizing
a motor
0.0
~
60.0
[sec]
This parameter applies the current to
a motor for the set time before motor
accelerates during sensorless vector
control
0.5
X
8-15
F20
1214
Jog
frequency
0.00
~
400.00
[Hz]
This parameter sets the frequency for
jog operation.
It cannot be set above max frequency
(F21)
10.00
O
8-3
F21
1)
1215
Max
frequency
40.00
~
400.00
[Hz]
Highest frequency the inverter can
output.
It is frequency reference for
Accel/Decel (See H70)
50.00
X
7-21
Caution