Chapter 11 Communication
11-4
Cx2000 AC Drive
11.6 Parameter code list <Common area> (note 1)
Address Parameter
Scale Unit R/W Allotment for Bits
0x0000
INV model
R
C: LTVF-Cx2000
0x0001
INV capacity
R
0000:0.1kW-1
0001:0.2kW-1
0002:0.4kW-1
0003:0.8kW-1
0004:1.5kW-1
0005:2.2kW-1
0006:0.1kW-2
0007:0.2kW-2
0008:0.4kW-2
0009:0.8kW-2
000A:1.5kW-2
000B:2.2kW-2
000C:3.7kW-2
000D:5.5kW-2
000E:7.5kW-2
000F:0.4kW-4
0010:0.8KW-4
0011:1.5KW-4
0012:2.2KW-4
0013:3.7KW-4
0014:5.5KW-4
0015:7.5KW-4
0x0002
Inverter input
voltage
-
-
R
0 : 1P 220V, 1 :3P 220V, 2
:
3P 440V
0x0003
Version
-
-
R
(Ex) 0x0010 : Version 1.0
0x0004
Parameter Lock -
-
R/W
0 : Lock(default), 1: Unlock
0x0005
Freq.
Reference
0.01
Hz
R/W
Starting freq. ~ Max. freq.
0x0006
Run Command
B7, B6: drive
type
R
B15, B14, B13 : Reserved
B12, B11, B10, B9, B8 : Freq. command
0
:
DRV-00
1
:
Reserved
2
:
Multi-step
speed 1
3
:
Multi-step
speed 2
4
:
Multi-step
speed 3
5
:
Multi-step
speed 4
6
:
Multi-step
speed 5
7
:
Multi-step
speed 6
8
:
Multi-step
speed 7
9
:
UP
10
:
DN
11
:
Up/Dn stop
12
:
V2 (knob) 13
:
V1
14
:
I
15
:
V2+I
16
:
V2+V1
17
:
JOG
R/W
18
:
PID
19
:
Commu.
0
:
Terminal
1
:
Keypad
3
:
Commu.
B5
:
Reversed B4
:
Emergency
Stop
B3
:
Reset
B2
:
Reverse
B1
:
Forward
B0
:
Stop
0x0007
Acceleration
Time
0.1
sec
R/W
See Function List
0x0008
Deceleration
0.1
sec
R/W
See Function List