Chapter 5 – Function list
5-4
Cx2000 AC Drive
rEF
2)
1110
PID control
standard
value
setting
0.00
~
400.00
[Hz] or
0
~
100[%]
If H58 is 0, it is expressed as a
[Hz] unit.
If H58 is 1, it is expressed as a
[%] unit.
In [Hz] unit, you can‟t set Max.
Frequency more than (F21).
In [%] unit, 100% means Max.
Frequency.
0.00
0
8-10
Fbk
2)
1111
PID control
Feedback
amount
0.00
~
400.00
[Hz] or
0
~
100[%]
It indicates a feedback amount in
PID control.
If H58 is 0, it is expressed as a
[Hz] unit.
If H58 is 1, it is expressed as a
[%] unit.
-
-
8-10
1)
: Only displayed when one of the Multi-function input terminals 1-5 [I17~I22] is set to “22”.
2)
: It is indicated when H49 (PID control selection) is 1.
Function group 1
LED
display
Address
for
comm
Parameter
name
Range
Description
Factory
defaults
Adj.
During
run
Page
F 0
1200
Jump code
0
~
72
Sets the parameter code number to
jump
1
O
4-5
F 1
1201
Forward/reverse
run disable
0
~
2
0
Fwd and rev run enable
0
X
7-10
1
Forward run disable
2
Reverse run disable
F 2
1202
Accel pattern
0
~
1
0
Linear
1
X
7-15
F 3
1203
Stop mode
select
1
S-curve
F 4
1204
Stop mode
Select
0
~
3
0
Decelerate to stop
0
X
7-20
1
DC brake to stop
2
Free run to stop
3
Power Braking stop
8-25
F 8
1)
1208
DC brake
start frequency
0.10
~
60.00
[Hz]
This parameter sets DC brake start
frequency.
It cannot be set below Start frequency
(F23).
0.50
X
8-1