Chapter 5 – Function list
-
5 8
Cx2000 AC Drive
Function group 1
LED
display
Address
for
comm
Parameter
name
Range
Description
Factory
defaults
Adj.
During
run
Page
F39
1227
Output voltage
adjustment
40.0
~
110.0
[%]
This parameter adjusts the amount of
output voltage.
The set value is the percentage of
input voltage.
100.0
X
7-18
F40
1228
Energy-saving
level
0
~
30[%]
This parameter decreases output
voltage according to load status.
0
0
8-17
F50
1232
Electronic
thermal
select
0
~
1
This parameter is activated when the
motor is overheated (time-inverse).
0
0
10-1
F51
1)
1233
Electronic
thermal level
for 1 minute
100
~
200[%]
This parameter sets max current
capable of flowing to the motor
continuously for 1 minute.
The set value is the percentage of
Motor rated current (H33).
It cannot be set below Electronic
thermal level for continuous (F52).
150
0
10-1
F52
1234
Electronic
thermal level
for continuous
50
~
150[%]
This parameter sets the amount of
current to keep the motor running
continuously.
It cannot be set higher than
Electronic thermal level for 1 minute
(F51).
100
0
F53
1235
Motor cooling
method
0
~
1
0
Standard motor having cooling
fan directly connected to the
shaft
0
0
1
A motor using a separate motor
to power a cooling fan.
F54
1236
Overload
warning level
30
~
150[%]
This parameter sets the amount of
current to issue an alarm signal at a
relay or multifunction output terminal
(see I55).
The set value is the percentage of
Motor rated current (H33).
150
0
10-2