Chapter 5 – Parameter list
5-1
Cx2000 AC Drive
5 Parameter list
Drive Group
Drive
Group
Address
for comm
Parameter
name
Set
range
Description
Factory
defaults
Adj.
during
run
Page
0.00
1100
Frequency
command
0.00
~
400.00
[Hz]
This parameter sets the frequency that
the inverter is commands to output.
During stop: frequency command
During run: output frequency
During Multi-step operation: It cannot be
set greater than F21(Max. frequency)
0.00
O
7-1
ACC
1101
Accel time
0.0
~
6000.0
[sec]
During Multi-Accel/Decel operation, this
parameter serves as Accel/Decel time
0.
20.0
O
7-12
dEC
1102
Decel time
20.0
O
7-12
drv
1103
Drive
Mode
0
~
3
0
RUN/STOP via RUN/STOP key
on the keypad
1
X
7-8
1
Terminal
operation
FX: motor forward run
RX: Motor reverse
run
7-8
2
FX: Run/Stop enable
RX: reverse rotation
select
7-9
3
RS-485 communication
7-9
Frq
1104
Frequency
Setting
Method
0
~
8
0
Digital
Keypad setting 1
0
X
7-1
1
Keypad setting 2
7-1
2
Analog
Panel Potentiometer
V2 set: 0 ~ 5 [V]
7-2
3
Terminal A1 (J1 to
V) : 0 ~ +10 [V]
7-2
4
Terminal A1 set (J1 to
I) :0 ~ 20 [mA]
7-3
5
Panel Potentiometer
V2 + Terminal A1 (J1
to I) setting
7-5
6
Panel Potentiometer
V2 + Terminal A1 (J1
to V) setting
7-5
Summary of Contents for C*2000 Series