Chapter 9 Monitoring
9-8
Cx2000 AC Drive
When setting I52 and I53 to 30.00 Hz and 10.00 Hz, respectively
2 : FDT-3
Activated when run frequency meets the following condition
Active condition: Absolute value (FDT level - run frequency) <= FDT Bandwidth/2
Group
Code
Name
Set Value
Range
Default
Unit
I/O Group
I52
Detected
Frequency
level
-
0.00 ~
400.00
30.00
Hz
I53
Detected
Frequency
Bandwidth
-
10.00
Cannot be set above Max frequency (F21).
When setting I52 and I53 to 30.0Hz and 10.0 Hz, respectively
25Hz
Freq.
MO
30Hz
Run command
Freq. setting
Freq.
MO
Run command
25Hz
30Hz
35Hz
50Hz
Summary of Contents for C*2000 Series
Page 163: ......