Chapter 8 Application
8-22
Cx2000 AC Drive
8.15 HD/ND select
Group
Code
Item
Set
Value
Setting
Range
Initial
Unit
Function Group 1 F72
HD/ND Select
-
0 ~ 1
0
-
Select rated capacity of inverter.
0: used for HD for constant torque application
1: used for ND for decreasing torque application
Rated current and applicable motors of inverter HD/ND refer to page 13-1, 13-2.
Caution
Rated current of three-phase inverter will be changed if F72 changes. And overload capacity of the
inverter is also different.
Single-phase inverter is applicable for HD occasion only.
8.16 Frequency setting and 2nd drive method select
Group
Code
Item
Set Value Setting range Initial
Unit
Drive group drv
Drive mode 1
-
0 ~ 3
1
Frq
Frequency mode 1
-
0 ~ 8
0
drv2
Drive mode 2
-
0 ~ 3
1
Frq2
Frequency mode 2
-
0 ~ 7
0
I/O group
I17~21
Multi-function input terminal P1
select
22
0 ~ 27
Drive mode 1 is used when the input set as 2
nd
source is not entered into multi-input (I17~I21)
Drive mode 2 can input frequency setting and drive command as a 2nd setting value by using
multi-input terminal. In case of driving away from inverter by communication, it is used when quit
the communication and operate by inverter.
The switching method for Drive mode 1 and Drive mode 2 is as follows
If multi-input terminal set as Drive mode 2 is off, it used as Drive mode 1 and frequency mode 1.
If multi-input terminal set as Drive mode 2 is on, it used as Drive mode 2 and frequency mode 2.