10/2016 - 4003537403 - MA OPTIWAVE 1010 R03 en
6.8 Status and error messages
6.8.1 Device status
Error data is given if you use PACTware
™
software with the appropriate DTM on a PC. The
software will show a symbol on the bottom left of the window if one or more error conditions are
found. This data agrees with NAMUR Recommendation NE 107 (Self-Monitoring and Diagnosis of
Field Devices) and VDI/VDE 2650.
Types of error message
For data on errors, refer to
Error handling on page 61.
NE 107 status
Type of
error
Description
Failure
Error
If an error message is shown on the Diagnosis
Diagnosis
Diagnosis
Diagnosis screen in the DTM, the current
output goes to the error signal value set in "Output range" in the Current output
Current output
Current output
Current output
menu.
Out of specification Warning
If a warning message is shown, there is no effect on the current output value.
Maintenance
NE 107
symbol
shown
NE 107
Status
Description
Error type
Possible errors
Failure
The device does not operate
correctly. The fault message
stays on.
Hardware error
Microwave error
Hardware error
EEPROM error (Config.)
Hardware error
EEPROM error (HART)
Hardware error
Output current calibration not valid
Error
No signal
Error
No measuring value
Error
Hardware error
Error
Current output set to error
Function
check
The device operates correctly,
but the measured value is
incorrect. This fault message is
only temporary. This symbol is
shown when the user configures
the device with the DTM or a
HART
®
Communicator.
—
—
Out of
specification
It is possible that the measured
value is unstable if the operating
conditions do not agree with the
device specification.
Warning
Signal weak
Warning
Signal strong
Warning
Spectrum quality bad
Warning
Measurement old
Maintenance
The device does not operate
correctly because of bad
environmental conditions (e.g.
build-up on the antenna). The
measured value is correct, but
maintenance is necessary a
short time after this symbol is
shown.
Warning
Sweep timing error
Warning
CPLD revision mismatch
Warning
Capacitor voltage low
Information
This status message is shown at
the same time as the error "no
measuring value".
Information
Peak lost in tank bottom
Information
Peak lost in blocking distance