6.4 Menu overview
Login/Logout
Login/Logout
Login/Logout
Login/Logout
It is necessary to use a password in this menu. Give a 6-digit code. This menu permits
the supervisor to set and lock device settings that are available to the supervisor and
change the supervisor password. The default password is 123412
123412
123412
123412.
This menu also permits personnel approved by the manufacturer to change device
settings in the service menu.
Import/Export
Import/Export
Import/Export
Import/Export
You can save all device settings to a workstation (Parameter menus: export). This data
can then be used to reset the device to its initial settings if an unwanted change is
made. If you want to operate other devices with the same settings, you can also load
this data into other devices (Parameter menus: import).
You can also save measurement data in a .DAT file to a workstation.
Information
Information
Information
Information
Read only. This menu gives data about the version of the hardware and software, the
device serial number and the customer order number.
Basic parameters
Basic parameters
Basic parameters
Basic parameters
The device must be attached to a bypass chamber to operate correctly. The
manufacturer usually sets the values for the minimum distance, the maximum
distance, the float offset and the internal diameter of the tube in the factory.
If the device does not have the correct settings in this menu, then these values can
have an effect on the performance of the device. If you make an incorrect selection of
the float, go to Application > Float offset calculation
Application > Float offset calculation
Application > Float offset calculation
Application > Float offset calculation in the DTM menu to calculate the
new float offset value.
Current output
Current output
Current output
Current output
You can make a selection from the parameters in the output function, output current
range and error delay lists.
Application
Application
Application
Application
Use this menu to change how the device operates when there are difficult process
conditions. Only approved personnel can change these parameters. The supervisor
can give the time constant, maximum tracing speed and multiple reflections to
identify the correct signal and follow it as level changes.
Float offset calculation
Float offset calculation
Float offset calculation
Float offset calculation
If the device does not have the correct float in the bypass
chamber, then the float offset value in the Basic
Basic
Basic
Basic
parameters
parameters
parameters
parameters menu is incorrect. An incorrect float offset
value can have an effect on the measurement data. Go to
Application > Float offset calculation
Application > Float offset calculation
Application > Float offset calculation
Application > Float offset calculation in the DTM menu to
calculate the new float offset value. Follow the
procedure.
HART
HART
HART
HART
Use this menu to change the tag name and read data (Device ID, Field device revision
etc.) that agrees with the HART
®
specification. You can also change the units of the
measured values.
Service
Service
Service
Service
This menu contains advanced device settings. It is locked with a password. The
handbook does not include data about the service menu.
DTM settings
DTM settings
DTM settings
DTM settings
Use this menu to change how the status display shows data at the top of the DTM
window.