2
DEVICE DESCRIPTION
14
OPTIWAVE 1010
www.krohne.com
10/2016 - 4003537403 - MA OPTIWAVE 1010 R03 en
2.1 Scope of delivery
2.2 Device description
OPTIWAVE 1010 is an FMCW radar designed for use with the BM 26 Advanced (a magnetic level
indicator or MLI) or a bypass chamber. If the device is used with an MLI, it measures the distance
to the float. If the device is used with a bypass chamber, it measures the distance to the surface
of the liquid. Radar is a non-contact technology. For more data about the measuring principle,
refer to
Measuring principle on page 68.
INFORMATION!
Do a check of the packing list to make sure that you have all the elements given in the order.
Figure 2-1: Scope of delivery
1
Device and measuring chamber
2
Quick Start
3
DVD-ROM (including Handbook, Quick Start, Technical Datasheet and related software)
INFORMATION!
You must use a float with BM26 Advanced magnetic level indicators that have the indicator
column, MS 40 limit switch or LT 40 analog transmitter options. If the device is installed on a
bypass chamber and the dielectric constant of the liquid is less than 3, you must use a float.
Figure 2-2: Radar level transmitter mounted on a magnetic (bypass) level indicator