5-12
SM-16007
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
7DEOH6SHFL¿FDWLRQVRI5HTXLUHG0DLQ3DUWV
NOTES:
1. Make the wiring to the terminals as short as possible.
2. Do not run the wirings too closely to the high voltage cable. Keep at least 12 in. (30cm) between the
wiring and the high voltage cable. (Crossing cables is okay.)
If it is necessary to run the wirings closer than 12 in. (30cm) to the high voltage cable, insert the low
voltage cable(s) into a metal tube and ground it at one end. If sealed wirings are used at the low voltage
wiring side, ground it at one end of the shielded wirings.
3. The maximum length should be within 230 ft. (70m).
Parts
6SHFL¿FDWLRQV
Remarks
Auxiliary Relay (X1, X2)
Mini-Power Relay, (Model: MY1F or MY2F)
made by OMRON
208V/230V
Change-Over Switch (SS2, SS3)
Manual Switch
208V/230V
3 Pin Connector Cord
Model: PCC-1A
(Connected to JST Connector, XARP-3)
Five Cords with
Connectors as One Set
Electric Wiring
(Inside of Unit)
Low Volt.
AWG22
lower than 24V
208/230V
AWG18-20
Electric Wiring
(Outside of Unit)
Low Volt.
AWG18-20
lower than 24V
208/230V
AWG14
Summary of Contents for YVAHP0721CW Series
Page 2: ......
Page 10: ...viii SM 16007 ...
Page 14: ......
Page 15: ...SM 16007 1 1 INSTALLATION 1 Installation ...
Page 163: ...SM 16007 2 1 OPERATION 2 Operation ...
Page 164: ...2 2 SM 16007 OPERATION Ɣ 5HIHU WR WKH 6HUYLFH 0DQXDO IRU QGRRU 8QLW RU RQWUROOHU ...
Page 165: ...SM 16007 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 284: ......
Page 285: ...SM 16007 4 1 MAINTENANCE 4 Maintenance ...
Page 360: ......
Page 390: ......
Page 391: ...SM 16007 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 400: ...6 10 SM 16007 FIELD WORK INSTRUCTIONS 0ROOLHU KDUW IRU 5 ft 3 l b ...
Page 401: ...SERVICE PARTS LIST SM 16007 7 1 7 Service Parts List ...
Page 416: ... 2016 Johnson Controls Inc SM 16007 Code No LIT 12012400 Issued November 2016 ...