5-20
SM-16007
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
NOTE:
Reduction rates are approximate, these may change slightly depending on the outdoor unit model.
(2) Night Shift (Low Noise) (Function Setting “ni”)
Press “PSW3” and select the setting condition “1” or “2” for the Night Shift (Low Noise) “
”. Then, this
function can be set. “ni”=1 reduces the upper limit of the outdoor fan rotation and the compressor frequency
as shown below in any operation. “ni”=2 is adapted only for cooling operation. In heating operation, “ni”=2
is same as “ni”=0.
The Night Shift operation should be used if the capacity has the margin to be allowed for the capacity
decrease and the low sound operation is required especially in the nighttime.
at Cooling Operation
Reduction Rate
of Upper Limit
Outdoor Fan
Radiation
72 (22)
77 (25)
65%
75%
90%
86 (30)
92 (33)
Outdoor Temperature [
o
F (
o
C)]
< Night Shift >
Reduction Rate of Maximum
Outdoor Fan Rotation
Compressor Frequency
“ ni ” Setting
Condition
Operation
Cooling
(Including Dry Operation)
Heating
Cooling
(Including Dry Operation)
Heating
0
No Effect
(Default Setting)
Not Changed
(=100%)
Not Changed
(=100%)
Not Changed
(=100%)
Not Changed
(=100%)
1
Night Shift1
Shown as below
Shown as below
60%
60%
2
Night Shift2
(only for Cooling)
Shown as below
Not Changed
60%
Not Changed
at Heating Operation
86 (30)
92 (33)
75%
90%
Outdoor Temperature [
o
F (
o
C)]
Reduction Rate
of Upper Limit
Outdoor Fan
Radiation
Summary of Contents for YVAHP0721CW Series
Page 2: ......
Page 10: ...viii SM 16007 ...
Page 14: ......
Page 15: ...SM 16007 1 1 INSTALLATION 1 Installation ...
Page 163: ...SM 16007 2 1 OPERATION 2 Operation ...
Page 164: ...2 2 SM 16007 OPERATION Ɣ 5HIHU WR WKH 6HUYLFH 0DQXDO IRU QGRRU 8QLW RU RQWUROOHU ...
Page 165: ...SM 16007 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 284: ......
Page 285: ...SM 16007 4 1 MAINTENANCE 4 Maintenance ...
Page 360: ......
Page 390: ......
Page 391: ...SM 16007 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 400: ...6 10 SM 16007 FIELD WORK INSTRUCTIONS 0ROOLHU KDUW IRU 5 ft 3 l b ...
Page 401: ...SERVICE PARTS LIST SM 16007 7 1 7 Service Parts List ...
Page 416: ... 2016 Johnson Controls Inc SM 16007 Code No LIT 12012400 Issued November 2016 ...