4.2 Installation Position
1. Horizontal
Installation
Locate the “Y” union pipe section on the same horizontal plane. (Inclination within 30
o
)
Make the straight section a minimum of 1.6ft (0.5m) after the vertical bend.
2. Vertical
Installation
Straight section of the pipe connection on the outdoor unit side is made as follows:
a) The collective pipe connection part is installed upward, the straight section must be a minimum of 1.6ft (0.5m).
b) The collective pipe connection part is installed downward, the straight section must be a minimum of 1.6ft (0.5m).
3. Piping Form from Multi-Kit to Indoor Unit
Upward
Downward
Horizontally
Total Straight Section
Min. 1.6ft (0.5m)
Inclination
within 30
o
30
o
A
Inclination
(View from A)
INCORRECT
Total Straight Section
Min. 1.6ft (0.5m)
Total Straight Section
Min. 1.6ft (0.5m)
Upward
Downward
Outdoor Unit
Outdoor Unit
Multi-Kit
Example: Recommended From each Indoor Unit to Multi-Kit have bending pipes and they will not tend to be deformed.
Bending Pipe
Connection Pipe
Example: Recommended
Indoor Unit
Straight piping does not allow for movement of the piping when it expands
or contracts.
Copper Piping will expand and contract due
to temperature changes in piping.
Copper Piping will expand and contract due to
temperature changes in piping.
NOTE:
[ Fixing for Liquid Piping, Low Pressure Gas Piping and High/Low Pressure Gas Piping ]
Multi-Kit
Install Horizontally
Due to the properties of copper piping
material, expansion and contraction take place
during seasons of heat and cold. Do not strap gas
refrigerant and piping containing liquids together
as deformation and cracks can result.
NOTE:
When on site piping is installed using
soft or hard copper make sure that the
piping is installed to allow for movement
of the piping. Caused by contraction
and expansion of the piping due to
temperature changes.
High/Low Pressure
Gas Piping
Installing Part for Piping
Liquid Piping
60
INSTALLATION
Summary of Contents for YVAHP0721CW Series
Page 2: ......
Page 10: ...viii SM 16007 ...
Page 14: ......
Page 15: ...SM 16007 1 1 INSTALLATION 1 Installation ...
Page 163: ...SM 16007 2 1 OPERATION 2 Operation ...
Page 164: ...2 2 SM 16007 OPERATION Ɣ 5HIHU WR WKH 6HUYLFH 0DQXDO IRU QGRRU 8QLW RU RQWUROOHU ...
Page 165: ...SM 16007 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 284: ......
Page 285: ...SM 16007 4 1 MAINTENANCE 4 Maintenance ...
Page 360: ......
Page 390: ......
Page 391: ...SM 16007 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 400: ...6 10 SM 16007 FIELD WORK INSTRUCTIONS 0ROOLHU KDUW IRU 5 ft 3 l b ...
Page 401: ...SERVICE PARTS LIST SM 16007 7 1 7 Service Parts List ...
Page 416: ... 2016 Johnson Controls Inc SM 16007 Code No LIT 12012400 Issued November 2016 ...