4-26
SM-16007
MAINTENANCE
TURN OFF all power source switches.
(5) Remove (G) solenoid valve coil connected to (H) solenoid valve body of the return oil circuit according
to Section 4.1.14.2 “Removing Solenoid Valve Coil”.
(6) Cut off (I) return oil circuit connecting with (J) accumulator pipe at the cutting position indicated in the
¿JXUHEHORZ
After that, remove remaining return oil circuit inside of (L) brazing for return oil circuit.
&XW,UHWXUQRLOFLUFXLWRIIIURP.RLOVHSDUDWRURXWOHWSRUWDWWKHSRLQWLQGLFDWHGLQWKH¿JXUH
Remove (I) return oil circuit from the unit. Then, remove (M) brazing for oil separator outlet.
NOTES:
1. When cutting (I) return oil circuit off, cut the closer part to (I) return oil circuit to prevent the
refrigerant oil remaining in (I) return oil circuit from spilling out.
2. When cutting (I) return oil circuit off, do not use a saw.
3. After cutting (I) return oil circuit off, remove the cut-off piping from (M) brazing for oil separator
outlet.
4. When removing (L) brazing for return oil circuit at the upper part of the return oil circuit and (M)
brazing for oil separator outlet, refrigerant oil may come out. Prepare the oil pan before the work to
receive the refrigerant oil.
Summary of Contents for YVAHP0721CW Series
Page 2: ......
Page 10: ...viii SM 16007 ...
Page 14: ......
Page 15: ...SM 16007 1 1 INSTALLATION 1 Installation ...
Page 163: ...SM 16007 2 1 OPERATION 2 Operation ...
Page 164: ...2 2 SM 16007 OPERATION Ɣ 5HIHU WR WKH 6HUYLFH 0DQXDO IRU QGRRU 8QLW RU RQWUROOHU ...
Page 165: ...SM 16007 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 284: ......
Page 285: ...SM 16007 4 1 MAINTENANCE 4 Maintenance ...
Page 360: ......
Page 390: ......
Page 391: ...SM 16007 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 400: ...6 10 SM 16007 FIELD WORK INSTRUCTIONS 0ROOLHU KDUW IRU 5 ft 3 l b ...
Page 401: ...SERVICE PARTS LIST SM 16007 7 1 7 Service Parts List ...
Page 416: ... 2016 Johnson Controls Inc SM 16007 Code No LIT 12012400 Issued November 2016 ...