SM-16007
5-25
EXTERNAL INPUT/OUTPUT AND FUNCTION SETTING
(10) Adjustment of Fan Rotation (Function Setting “Fo”)
Press “PSW3” and select the setting condition “0” to “2” at Adjustment of Fan Rotation “
”, so Adjustment
of Fan Rotation can be set. If the outdoor unit fans make a whining sound in an instance of multiple
installations, set this function to the relevant outdoor units.
(11) Energy Saving Mode (Function Setting “F1”)
Press “PSW3” and select the setting condition “0” to “1”, so that Energy Saving Mode “
” can be set.
This function is available by setting to “1” to lower the compressor frequency upper limit and reduce
energy consumption. The heating capacity will be reduced during Energy Saving Mode is set, so utilize this
mode only when the extra capacity to the load is available. Energy Saving Mode can be set during heating
operation.
NOTE:
By setting this function, the outdoor fan rotation is slightly reduced, so the outdoor unit capacity may
decrease and the operation range may be limited.
"Fo" Setting Condition
Adjustment of Fan Rotation
0
Not Available (Default Setting)
1
-12 rpm
2
-24 rpm
"F1" Setting Condition
Energy Saving
0
Initial Setting (Not Available)
1
Available (Compressor Frequency 80%)
Summary of Contents for YVAHP0721CW Series
Page 2: ......
Page 10: ...viii SM 16007 ...
Page 14: ......
Page 15: ...SM 16007 1 1 INSTALLATION 1 Installation ...
Page 163: ...SM 16007 2 1 OPERATION 2 Operation ...
Page 164: ...2 2 SM 16007 OPERATION Ɣ 5HIHU WR WKH 6HUYLFH 0DQXDO IRU QGRRU 8QLW RU RQWUROOHU ...
Page 165: ...SM 16007 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 284: ......
Page 285: ...SM 16007 4 1 MAINTENANCE 4 Maintenance ...
Page 360: ......
Page 390: ......
Page 391: ...SM 16007 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 400: ...6 10 SM 16007 FIELD WORK INSTRUCTIONS 0ROOLHU KDUW IRU 5 ft 3 l b ...
Page 401: ...SERVICE PARTS LIST SM 16007 7 1 7 Service Parts List ...
Page 416: ... 2016 Johnson Controls Inc SM 16007 Code No LIT 12012400 Issued November 2016 ...