SM-16007
4-27
MAINTENANCE
TURN OFF all power source switches.
Tool
Adjustable Wrench
(8) Cover the hole of (L) brazing for return oil circuit using tape.
Connect a charging hose to (M) brazing for oil separator outlet. Then, charge nitrogen (22 psi (0.15
03DIURPWKHXSSHUXQLRQRI'ORZSUHVVXUHDFFHVVSRUWDQGUHFRYHUUHIULJHUDQWRLOLQWKH.RLO
separator, applying pressure.
NOTE:
In an instance where the unit has two return oil circuits and two oil separators, collect the refrigerant oil
from one oil separator and then from the other.
(9) Stop charging nitrogen after the refrigerant oil has completely been collected and connect the return oil
SLSH$IWHUFRQQHFWLQJWKHSLSHSHUIRUPWKHQLWURJHQSUHVVXUL]DWLRQIURP'ORZSUHVVXUHDFFHVVSRUW
'XULQJWKHZRUNFKHFNWKDWWKHRLOGRHVQRWVSLOORXWIURPWKHÀDUHQXWFRQQHFWLRQDQGEUD]HMRLQW
3HUIRUPYDFXXPLQJIURP'ORZSUHVVXUHDFFHVVSRUWDQGDGGWKHVDPHTXDQWLW\RIRLOWKDWZDV
collected from (C) access port for recovering refrigerant oil.
NOTE:
If replacing the return oil circuit only, procedures (8) and (9) are not required.
:KHQWKHSURFHGXUHVKDYHEHHQFRPSOHWHGSHUIRUPYDFXXPLQJDJDLQIURP'ORZSUHVVXUHDFFHVV
port and recharge the refrigerant. After recharging, open the stop valves.
NOTES:
1. Use a clean charging hose.
2. Charge the refrigerant oil in a short amount of time (within approximately 20 minutes).
Use a container with a small opening so that the refrigerant oil will not absorb moisture from the
atmosphere.
(K) Oil Separator
(M) Brazing for
Oil Separator Outlet
(I) Return Oil Circuit
(For Inverter Compressor)
(I) Return Oil Circuit
(Remove after cutting.)
Details of Cutting Position
(I) Return Oil Circuit
(For Constant Speed Compressor)
(L) Brazing for Return Oil Circuit
(G) Solenoid Valve Coil
(J) Accumulator Pipe
(H) Solenoid Valve Body
Cut
(I) Return Oil Circuit
Details of Cutting Position
Cut
(J) Accumulator Pipe
Summary of Contents for YVAHP0721CW Series
Page 2: ......
Page 10: ...viii SM 16007 ...
Page 14: ......
Page 15: ...SM 16007 1 1 INSTALLATION 1 Installation ...
Page 163: ...SM 16007 2 1 OPERATION 2 Operation ...
Page 164: ...2 2 SM 16007 OPERATION Ɣ 5HIHU WR WKH 6HUYLFH 0DQXDO IRU QGRRU 8QLW RU RQWUROOHU ...
Page 165: ...SM 16007 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 284: ......
Page 285: ...SM 16007 4 1 MAINTENANCE 4 Maintenance ...
Page 360: ......
Page 390: ......
Page 391: ...SM 16007 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 400: ...6 10 SM 16007 FIELD WORK INSTRUCTIONS 0ROOLHU KDUW IRU 5 ft 3 l b ...
Page 401: ...SERVICE PARTS LIST SM 16007 7 1 7 Service Parts List ...
Page 416: ... 2016 Johnson Controls Inc SM 16007 Code No LIT 12012400 Issued November 2016 ...