1-30
SM-16007
INSTALLATION
6.2 Piping Connection Work
Comply with the restrictions for refrigerant piping (permissible length, height difference) in Section 6.5 “Piping
Work Conditions” and “Piping Branch Restriction”. If not, the outdoor unit can become damaged or fail.
The stop valves will be closed completely (factory-setting) when refrigerant piping connections are performed.
Do not open these stop valves until all the refrigerant piping connections, airtight testing, and vacuuming
have been completed.
6.2.1 Stop Valve
< Gas Valve >
(1) Make sure that all the spindles are closed completely.
(2) Connect the charging hose to the service port and release the gas inside the piping.
(3) Cut the end of the closing pipe and ensure that no residual gas exists inside the gas piping.
5HPRYHWKHFORVLQJSLSHIURPWKHEUD]LQJSRUWLRQZLWKDWRUFK%HFDUHIXOWKDWWKHÀDPHGRHVQ¶WEXUQ
the stop valve.
Ɣ 5HPRYHJDVLQVLGHWKHFORVLQJSLSHEHIRUHWKHEUD]LQJZRUNLVSHUIRUPHG
,IWKHEUD]LQJ¿OOHUPHWDOPHOWVZLWKUHVLGXDOJDVLQVLGHWKHSLSLQJZLOOH[SORGHDQGLQMXULHVFDQ
result.
Ɣ 'RQRWH[SRVHVXUURXQGLQJSDUWVDQGWKHRLOUHWXUQSLSHRIWKHFRPSUHVVRUWRÀDPHVZKHQDWRUFK
LVXVHG,IWKHRLOUHWXUQSLSLQJLVH[SRVHGWRWKH¿UHKLJKWHPSHUDWXUHRLOZLOOVSXUWDQGFDXVHD
¿UHRULQMXU\
Figure 6.1
Stop Valve for
Liquid Pipe
End of Closing Pipe
Service Port
Stop Valve for
Gas Pipe
Closing Pipe
Cut
Detail of Closing Pipe
Soundproof
Cover
Compressor
Oil Return Pipe
Torch
Metal Plate
Closing Pipe
Stop Valve
Body
Field-Work Side
Summary of Contents for YVAHP0721CW Series
Page 2: ......
Page 10: ...viii SM 16007 ...
Page 14: ......
Page 15: ...SM 16007 1 1 INSTALLATION 1 Installation ...
Page 163: ...SM 16007 2 1 OPERATION 2 Operation ...
Page 164: ...2 2 SM 16007 OPERATION Ɣ 5HIHU WR WKH 6HUYLFH 0DQXDO IRU QGRRU 8QLW RU RQWUROOHU ...
Page 165: ...SM 16007 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 284: ......
Page 285: ...SM 16007 4 1 MAINTENANCE 4 Maintenance ...
Page 360: ......
Page 390: ......
Page 391: ...SM 16007 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 400: ...6 10 SM 16007 FIELD WORK INSTRUCTIONS 0ROOLHU KDUW IRU 5 ft 3 l b ...
Page 401: ...SERVICE PARTS LIST SM 16007 7 1 7 Service Parts List ...
Page 416: ... 2016 Johnson Controls Inc SM 16007 Code No LIT 12012400 Issued November 2016 ...