SM-16007
3-49
TROUBLESHOOTING
Alarm
Code
Abnormality of Power Source Phase
O
7KH581LQGLFDWRUUHGÀDVKHV
O
The indoor unit number (refrigerant cycle number - address number), the alarm code, the model code*
1)
,
the model name*
1)
and the number of connected indoor units are displayed on the LCD. The indoor unit
number and the alarm code are displayed on the 7-segment display of the outdoor unit PCB.
*1) Except for some models.
+
This alarm code is displayed when the main power source phase is reversely connected or one phase
is not connected.
Correctly connect each phase
of power source.
No
Open Phase
(Is there any phase not connected?)
No
Yes
O.U. PCB is normal.
O.U. PCB is normal.
O.U. PCB is normal.
Voltage for unit to
be suspended.
Running Voltage:
"B" V
Starting Voltage:
Less than "A" V
Abnormality with Power Source.
Is there any excessive voltage
decrease at power source?
Yes
Correctly connect each phase
of power source.
Faulty O.U. PCB.
No
Reverse Phase Connection?
Yes
Cause
Check Item
Action
(Turn OFF Main Switch)
Event
Activation of
Reverse Phase
Sensor in
Outdoor Unit
Check it according
to electrical wiring
in Section 3.1.1.
Replace wires, repair
and tighten screws
or correct wiring.
Reverse or Open Phase
Replace O.U. PCB
if faulty.
Faulty O.U. PCB
Check Item
Power Supply
“A”
“B”
208-230V/60Hz
177
188 to 253
460V/60Hz
391
414 to 506
O.U. PCB: Outdoor Unit PCB
Summary of Contents for YVAHP0721CW Series
Page 2: ......
Page 10: ...viii SM 16007 ...
Page 14: ......
Page 15: ...SM 16007 1 1 INSTALLATION 1 Installation ...
Page 163: ...SM 16007 2 1 OPERATION 2 Operation ...
Page 164: ...2 2 SM 16007 OPERATION Ɣ 5HIHU WR WKH 6HUYLFH 0DQXDO IRU QGRRU 8QLW RU RQWUROOHU ...
Page 165: ...SM 16007 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 284: ......
Page 285: ...SM 16007 4 1 MAINTENANCE 4 Maintenance ...
Page 360: ......
Page 390: ......
Page 391: ...SM 16007 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 400: ...6 10 SM 16007 FIELD WORK INSTRUCTIONS 0ROOLHU KDUW IRU 5 ft 3 l b ...
Page 401: ...SERVICE PARTS LIST SM 16007 7 1 7 Service Parts List ...
Page 416: ... 2016 Johnson Controls Inc SM 16007 Code No LIT 12012400 Issued November 2016 ...