3-36
SM-16007
TROUBLESHOOTING
PROCEDURE REMINDERS:
• Measure the insulation resistance of a failed compressor.
Do not perform an emergency operation when the insulation resistance is 0
:
The other compressors may be damaged because there is a possibility that refrigerant oil is oxidized.
• Total operating capacity of indoor unit should be 90kBtu/h and over.
(Less than 90kBtu/h: Forced stoppage)
• In this emergency operation, compressor frequency cannot be controlled normally.
Therefore, an alarm code “07”, “43”, “44”, “45” or “47” may be indicated on the LCD.
7KLVHPHUJHQF\RSHUDWLRQPD\QRWSURYLGHVXI¿FLHQWFRROLQJDQGKHDWLQJFDSDFLW\
• This operation is a temporary emergency operation when the inverter compressor is damaged.
Therefore, replace it with the new one as soon as possible.
• Turn OFF DSW5-No.1 and No.2 of the outdoor unit PCB after replacing the compressor.
If this setting is not performed, the inverter compressor will be damaged.
(b) Operation Condition
< Indoor Unit Operation Capacity >
The compressor is forced to stop for compressor protection under the following condition:
Total Capacity of Thermo ON I.U. < 50% of O.U. Capacity and
Total Capacity of Thermo ON I.U. < 90kBtu/h
$ODFNRIDWKHUPR21LQGRRUXQLWPD\OHDGWRD¿[HGVSHHGFRPSUHVVRUIDLOXUH
because the compressor is operated and stopped repeatedly.)
NOTE:
Thermo-ON: The outdoor unit and some indoor units are running.
Thermo-OFF: The outdoor unit and some indoor units stay on, but don’t run.
Summary of Contents for YVAHP0721CW Series
Page 2: ......
Page 10: ...viii SM 16007 ...
Page 14: ......
Page 15: ...SM 16007 1 1 INSTALLATION 1 Installation ...
Page 163: ...SM 16007 2 1 OPERATION 2 Operation ...
Page 164: ...2 2 SM 16007 OPERATION Ɣ 5HIHU WR WKH 6HUYLFH 0DQXDO IRU QGRRU 8QLW RU RQWUROOHU ...
Page 165: ...SM 16007 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 284: ......
Page 285: ...SM 16007 4 1 MAINTENANCE 4 Maintenance ...
Page 360: ......
Page 390: ......
Page 391: ...SM 16007 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 400: ...6 10 SM 16007 FIELD WORK INSTRUCTIONS 0ROOLHU KDUW IRU 5 ft 3 l b ...
Page 401: ...SERVICE PARTS LIST SM 16007 7 1 7 Service Parts List ...
Page 416: ... 2016 Johnson Controls Inc SM 16007 Code No LIT 12012400 Issued November 2016 ...