SM-16007
4-39
MAINTENANCE
4.1.19 Removing Other Electrical Components
TURN OFF all power source switches.
NOTES:
1. Apply conductive heat transfer paste or silicon grease (Service Part No.: P22760) slightly over the contact
VXUIDFHRIWKH¿QZKHQUHSODFLQJWKHFRPSRQHQWVRIWKHUDGLDWLRQ¿QVXFKDVWUDQVLVWRUPRGXOH,30
GLRGHPRGXOH'0DQGIDQFRQWUROOHU)$10
2. Match the terminal numbers with the mark band numbers when reassembling. If incorrectly connected,
malfunction may occur or the electrical components may be damaged.
3. The U and V-Phases of the power source cables for inverter compressor (MC1) should be passed through
the current sensor (CTU and CTV) of the inverter module (PCB2) completely.
Connect the U-Phase of the power source cable with the U-Phase side (CTU), and the V-Phase with the
V-Phase side (CTV) of the current sensor. Not doing so may cause equipment malfunction or failure.
4. When securing PCBs or sheet metal for PCBs, protect the electric wiring from being caught on the sheet
metal or the electrical components.
5. Make sure to use screws, bushes and collars when securing PCBs for the inverter compressor.
Not doing so may cause equipment malfunction.
:KHQUHSODFLQJWKH3&%IRUFRPPXQLFDWLRQVHWWKH',3VZLWFKHVWKHVDPHDVEHIRUHUHSODFLQJWKH3&%
An incorrect setting will cause a malfunction. Refer to the instruction manual attached with servicing the
PCB.
'RQRWDSSO\H[FHVVLYHIRUFHWRWKHHOHFWULFDOFRPSRQHQWVRQWKH3&%RUWKH3&%LWVHOI,WPD\OHDGWR
PCB malfunction.
:KHQUHSODFLQJWKHIDQFRQWUROOHUVHWWKH',3VZLWFKHVWKHVDPHDVEHIRUHUHSODFLQJWKHIDQFRQWUROOHU
An incorrect setting will cause a malfunction.
Summary of Contents for YVAHP0721CW Series
Page 2: ......
Page 10: ...viii SM 16007 ...
Page 14: ......
Page 15: ...SM 16007 1 1 INSTALLATION 1 Installation ...
Page 163: ...SM 16007 2 1 OPERATION 2 Operation ...
Page 164: ...2 2 SM 16007 OPERATION Ɣ 5HIHU WR WKH 6HUYLFH 0DQXDO IRU QGRRU 8QLW RU RQWUROOHU ...
Page 165: ...SM 16007 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 284: ......
Page 285: ...SM 16007 4 1 MAINTENANCE 4 Maintenance ...
Page 360: ......
Page 390: ......
Page 391: ...SM 16007 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 400: ...6 10 SM 16007 FIELD WORK INSTRUCTIONS 0ROOLHU KDUW IRU 5 ft 3 l b ...
Page 401: ...SERVICE PARTS LIST SM 16007 7 1 7 Service Parts List ...
Page 416: ... 2016 Johnson Controls Inc SM 16007 Code No LIT 12012400 Issued November 2016 ...