SM-16007
1-43
INSTALLATION
Ɣ 3LSLQJ%UDQFK5HVWULFWLRQ
In the following instances, there is no limit to the number of main piping branches.
,IWKHSLSLQJOHQJWK/IURPWKH0XOWL.LWDWWKH¿UVWEUDQFKWRWKHIDUWKHVWLQGRRUXQLWLVRYHUIWP
IROORZWKHLQVWUXFWLRQVEHORZZKHQSHUIRUPLQJWKH¿HOGVXSSOLHGSLSLQJZRUN
(Example 1) : Installation with Main Piping Branch (
7
)
3LSLQJOHQJWKIURPWKH0XOWL.LWDWWKH¿UVWEUDQFKWRWKHWHUPLQDOLQGRRUXQLWLVZLWKLQIW
90m).
(1) If the pipe length L2 is over 131.2 ft (40m), the size of gas and liquid pipes “b and c” or “g and h”
should be selected according to Table
4
below, “Diameter of Pipe after First Branch”.
* If the size of (a) is smaller than the size of (b, g) after selecting the size according to Table
4
below,
“Diameter of Pipe after First Branch”, adjust the size of (a) so it is the same size as (b, g).
If the size of (a) is larger than the size indicated in Table
3
below, “Main Pipe Diameter” of (Equivalent
Piping Length > 328.1ft), adjust the size of (a) so it is the same size according to Table
3
below, “Main
Pipe Diameter” of (Equivalent Piping Length > 328.1ft).
In this instance, if the size of (b, c, g, h) is larger than the size of each before the branch, adjust the
size of (b, c, g, h) to the same size as each before the branch.
7KHGLIIHUHQFHEHWZHHQWKHSLSLQJOHQJWKIURPWKH¿UVWEUDQFKWRWKHIDUWKHVWLQGRRUXQLWDQGWKHSLSLQJ
OHQJWKIURPWKH¿UVWEUDQFKWRWKHFORVHVWLQGRRUXQLWPXVWEHZLWKLQIWP
* (g+h+j)-(b+d)<131.2 ft (40m)
(Example 2): Installation without Main Piping Branch (
7
)
3LSLQJOHQJWKIURPWKH0XOWL.LWDWWKH¿UVWEUDQFKWRWKHWHUPLQDOLQGRRUXQLWLVZLWKLQIW
90m).
(1) If the pipe length L2 is over 131.2 ft (40m), the size of gas and liquid pipes “b, d and f” should be
selected according to Table
4
below, “Diameter of Pipe after First Branch”.
* If the size of (a) is smaller than the size of (b) after selecting the size according to Table
4
below,
“Diameter of Pipe after First Branch”, adjust the size of (a) so it is the same size as (b).
If the size of (a) is larger than the size indicated in Table
3
below, “Main Pipe Diameter” of (Equivalent
Piping Length > 328.1ft), adjust the size of (a) so it is the size according to Table
3
below, “Main
Pipe Diameter” of (Equivalent Piping Length > 328.1ft).
In this case, if the size of (b, d, f) is larger than the size of each before the branch, adjust the size of (b,
d, f) to the same size as each before the branch.
(
7
): Main Piping Branch:
Both branches of piping from a Multi-Kit are
connected to the next Multi-Kits.
L2
b
a
d
c
e
g
i
f
h
Piping Length from the Multi-Kit at the first branch
to the terminal Indoor Unit is within 131.2 ~ 295.3 ft
First Branch
Multi-Kit
Terminal
Indoor Unit
The Farthest Indoor Unit
from the First Branch
The Closest Indoor Unit
from the First Branch
b
a
First Branch
c
e
d
f
i
j
k
h
g
Terminal
Indoor Unit
Terminal
Indoor Unit
Piping Length from the Multi-Kit at the first branch
to the terminal Indoor Unit is within 131.2 ~ 295.3 ft
Multi-Kit
The Closest Indoor Unit
from the First Branch
ࠉ
The Farthest Indoor Unit
from the First Branch
ࠉ
L2
L2
Indoor Unit
Main Branch
a
b
c
e
f
d
Summary of Contents for YVAHP0721CW Series
Page 2: ......
Page 10: ...viii SM 16007 ...
Page 14: ......
Page 15: ...SM 16007 1 1 INSTALLATION 1 Installation ...
Page 163: ...SM 16007 2 1 OPERATION 2 Operation ...
Page 164: ...2 2 SM 16007 OPERATION Ɣ 5HIHU WR WKH 6HUYLFH 0DQXDO IRU QGRRU 8QLW RU RQWUROOHU ...
Page 165: ...SM 16007 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 284: ......
Page 285: ...SM 16007 4 1 MAINTENANCE 4 Maintenance ...
Page 360: ......
Page 390: ......
Page 391: ...SM 16007 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 400: ...6 10 SM 16007 FIELD WORK INSTRUCTIONS 0ROOLHU KDUW IRU 5 ft 3 l b ...
Page 401: ...SERVICE PARTS LIST SM 16007 7 1 7 Service Parts List ...
Page 416: ... 2016 Johnson Controls Inc SM 16007 Code No LIT 12012400 Issued November 2016 ...