TROUBLESHOOTING
Alarm
Code
Activation of Protection Device for Indoor Fan Motor
(Wall Mount Type)
O
7KH581LQGLFDWRUUHGÀDVKHV
O
The indoor unit number (refrigerant cycle number - address number), the alarm code, the model code*
1)
,
the model name*
1)
and the number of connected indoor units are displayed on the LCD. The indoor unit
number and the alarm code are displayed on the 7-segment display of the outdoor unit PCB.
*1) Except for some models.
+
7KLVDODUPFRGHLVGLVSOD\HGZKHQWKHLQGRRUIDQPRWRUURWDWHVDWOHVVWKDQUSPIRU¿YHVHFRQGVIRU
40 seconds during auto swing operation) three times in 30 minutes during the operation.
Failure of I.U. PCB
(*1)
The electrical source for I.U. PCB
is not supplied when LED4
is turned OFF.
(*2)
Abnormal voltage is supplied
to fan motor.
Is LED4 on
I.U. PCB OFF?
(*1)
Is LED1 on
I.U. PCB OFF?
(*2)
Check connectors PCN500
and PCN550 on I.U. PCB.
Yes
Replace I.U. PCB.
No
No
No
No
Failure of I.U. PCB
Replace I.U. PCB.
Is fan motor
speed control command to
fan motor sent correctly?
(*5)
Yes
Yes
Failure of I.U. PCB
Failure of I.U. PCB
Failure of I.U. PCB
Is DC power
output of I.U. PCB
normal? (*3)
Replace I.U. PCB.
Replace I.U. PCB.
Replace I.U. PCB.
(*3)
Measure the voltage between
VCC15 and VDC (15V+10%) with a tester.
Yes
Yes
No
Occurrence of
Alarm Code “19”
(*4)
Measure the voltage of the following check points with a tester.
Between VCC05 and GND: 5V+4%
Between VCC13 and GND: 13.1V+10%
(Normal Voltage: DC280V)
No
Failure of Fan Motor
Replace Fan Motor
Yes
Failure of I.U. PCB
Failure of Fan Motor
Is speed pulse
signal to I.U. PCB
sent correctly?
(*6)
Replace I.U. PCB.
Replace Fan Motor.
No
Does Fan
Motor run?
Yes
(*5)
(*6)
(*6) Start the operation with PCN550 on I.U. PCB connected.
It functions normally if several volts are generated between
No.2 pin of PC4 and VDC- (check point).
(NOTE)
Even if the operation is stopped, approx. 0.2V can be generated.
Yes
Check that 208/230V is
applied between
L1 and N of TB1.
NOTE:
Turn OFF the power source completely
before connector checking.
Otherwise, it may cause DC fan motor failure.
(Built-in PCB for DC fan motor may be damaged.)
(*5) Start the operation with PCN550 on I.U. PCB disconnected.
It functions normally if more than 1V is generated between No.4
pin of PCN550 and VDC- (check point) for approx. 10 seconds
after start of operation.
(NOTES)
1. Even if the operation is stopped, 0.3 to 0.4V can be generated.
2. To perform the operation “
H
”, no voltage will be generated
sequentially 10 seconds after start of operation.
Is DC power
output of I.U. PCB
normal? (*4)
l
Perform the following check after setting
the airflow volume to “HIGH”.
l
A high voltage is applied to electrical parts.
Perform the check carefully to prevent
an electric shock.
Ɣ
Ɣ
Summary of Contents for YVAHP0721CW Series
Page 2: ......
Page 10: ...viii SM 16007 ...
Page 14: ......
Page 15: ...SM 16007 1 1 INSTALLATION 1 Installation ...
Page 163: ...SM 16007 2 1 OPERATION 2 Operation ...
Page 164: ...2 2 SM 16007 OPERATION Ɣ 5HIHU WR WKH 6HUYLFH 0DQXDO IRU QGRRU 8QLW RU RQWUROOHU ...
Page 165: ...SM 16007 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 284: ......
Page 285: ...SM 16007 4 1 MAINTENANCE 4 Maintenance ...
Page 360: ......
Page 390: ......
Page 391: ...SM 16007 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 400: ...6 10 SM 16007 FIELD WORK INSTRUCTIONS 0ROOLHU KDUW IRU 5 ft 3 l b ...
Page 401: ...SERVICE PARTS LIST SM 16007 7 1 7 Service Parts List ...
Page 416: ... 2016 Johnson Controls Inc SM 16007 Code No LIT 12012400 Issued November 2016 ...