Temperature
Maximum
Minimum
Cooling
Operation
Indoor
89
o
F DB/73
o
F WB (32
o
C DB/23
o
C WB)
69
o
F DB/59
o
F WB (21
o
C DB/15
o
C WB)
Outdoor
118
o
F DB (48
o
C DB)
*1), *2)
14
o
F DB (-10
o
C DB)
*3), *4)
Heating
Operation
Indoor
80
o
F DB (27
o
C DB)
59
o
F DB ( 15
o
C DB)
Outdoor
59
o
F WB (15
o
C WB)
*5)
-4
o
F WB (-20
o
C WB)
*6)
DB: Dry Bulb, WB: Wet Bulb
*1) When the outdoor air temperature is 100
o
F DB (38
o
C DB) or more and the outdoor unit operation capacity
ratio is 100% or more, the outdoor unit will be Thermo-OFF to protect the compressor from failure.
*2) When the outdoor air temperature is 109
o
F (43
o
C) or more during the outdoor unit cooling operation, the
maximum connectable indoor unit capacity ratio is 100%.
*3) When the outdoor air temperature is 23
o
F (-5
o
C) or less during the outdoor unit cooling operation, the
minimum connectable indoor unit capacity is 18,000 Btu/h.
In this case, install the snow protection hood (optional).
*4) When operating the outdoor unit under the low cooling load conditions and in the low outdoor air
temperature, (applox. 50
o
F DB (10
o
C DB) or less), the indoor unit will be Thermo-OFF to prevent the heat
exchanger of the indoor unit from being frosted.
*5) When operating the outdoor unit under the low heating load conditions and the outdoor temperature is
59
o
F DB (15
o
C DB) or more, the outdoor unit will be Thermo-OFF to protect the compressor from failure.
*6) Operation in the outdoor temperature of 5~-4
o
F WB (-15~20
o
C WB) is assumed to limited conditions such
as start-up in early morning.
Long time operation in this condition may shorten the life of the compressor.
Important Notice
Ɣ
Johnson Controls Inc. pursues a policy of continuing improvement in design and performance in its
products. As such, Johnson Controls Inc. reserves the right to make changes at any time without prior
notice.
Ɣ
Johnson Controls Inc. cannot anticipate every possible circumstance that might involve a potential
hazard.
Ɣ
This heat pump air conditioning unit is designed for standard air conditioning applications only. Do not
use this unit for anything other than the purposes for which it was intended for.
Ɣ 7KHLQVWDOOHUDQGV\VWHPVSHFLDOLVWVKDOOVDIHJXDUGDJDLQVWOHDNDJHLQDFFRUGDQFHZLWKORFDOSLSH¿WWHU
and electrical codes. The following standards may be applicable, if local regulations are not available.
International Organization for Standardization: (ISO 5149 or European Standard, EN 378). No part of
this manual may be reproduced in any way without the expressed written consent of Johnson Controls
Inc.
Ɣ
This heat pump air conditioning unit will be operated and serviced in the United States of America and
comes with a full complement of the appropriate Safety, Danger, and Caution, warnings.
Ɣ
If you have questions, please contact your distributor or dealer.
Ɣ
This manual provides common descriptions, basic and advanced information to maintain and service
this heat pump air conditioning unit which you operate as well for other models.
Ɣ 7KLVKHDWSXPSDLUFRQGLWLRQLQJXQLWKDVEHHQGHVLJQHGIRUDVSHFL¿FWHPSHUDWXUHUDQJH)RURSWLPXP
performance and long life, operate this unit within the range limits according to the table below.
Ɣ
This manual should be considered as a permanent part of the air conditioning equipment and should
remain with the air conditioning equipment.
Summary of Contents for YVAHP0721CW Series
Page 2: ......
Page 10: ...viii SM 16007 ...
Page 14: ......
Page 15: ...SM 16007 1 1 INSTALLATION 1 Installation ...
Page 163: ...SM 16007 2 1 OPERATION 2 Operation ...
Page 164: ...2 2 SM 16007 OPERATION Ɣ 5HIHU WR WKH 6HUYLFH 0DQXDO IRU QGRRU 8QLW RU RQWUROOHU ...
Page 165: ...SM 16007 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 284: ......
Page 285: ...SM 16007 4 1 MAINTENANCE 4 Maintenance ...
Page 360: ......
Page 390: ......
Page 391: ...SM 16007 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 400: ...6 10 SM 16007 FIELD WORK INSTRUCTIONS 0ROOLHU KDUW IRU 5 ft 3 l b ...
Page 401: ...SERVICE PARTS LIST SM 16007 7 1 7 Service Parts List ...
Page 416: ... 2016 Johnson Controls Inc SM 16007 Code No LIT 12012400 Issued November 2016 ...