3-12
SM-16007
TROUBLESHOOTING
Ɣ
6HWWLQJRI(QG7HUPLQDO5HVLVWDQFH
The factory setting for the No. 1 pin of DSW10 (for the setting of end
terminal resistance) is in the “ON” position.
If there is one number in the same communication line (H-LINK ll),
set all No. 1 pins of DSW10 in the “OFF” position except the main
outdoor Unit A.
Ɣ
'6:6HWWLQJIRU5DWHG9ROWDJH
DSW7 is used for setting of rated voltage for the outdoor unit as
shown at the right.
When the site power source voltage is different from the factory
setting, DSW7 setting is required.
NOTE:
The same voltage setting is required for the main unit and sub unit(s).
Verify the DSW7 DIP switch settings match the same voltage as the
power source.
If there is more than one refrigerant cycle in the same communication line (H-LINK ll), set all No. 1 pins of
DSW10 in the “OFF” position except one outdoor unit.
1 2
1 2
ON
OFF
ON
OFF
Factory Setting
Cancellation
DSW10
Setting of End Terminal Resistance
Voltage
DSW7 Setting
208V
230V
460V
1 2 3 4
ON
OFF
1 2 3 4
ON
OFF
1 2 3 4
ON
OFF
1 2
DSW10
1 2
DSW10
1 2
DSW10
Communication Line
(No Polarity)
H-LINK II
Outdoor Unit
(Unit Combination)
Indoor
Unit
Cancel the end terminal setting.
Set the end terminal.
Unit A
(Main)
Unit B
(Sub)
Unit C
(Sub)
1 2
DSW10
1 2
DSW10
1 2
DSW10
1 2
DSW10
1 2
DSW10
1 2
DSW10
1 2
DSW10
Communication Line
(No Polarity)
H-LINK II
Outdoor Unit
(Unit Combination)
Indoor
Unit
Wired Controller
Indoor
Unit
Indoor
Unit
Indoor
Unit
Outdoor Unit
(Base Unit)
Cancel the end terminal.
Cancel the end terminal setting.
Cancel the end terminal.
Cancel the end terminal.
Outdoor unit being
set end terminal
Set the end terminal.
Outdoor Unit
(Unit Combination)
Outdoor Unit
(Base Unit)
Unit A
(Main)
Unit B
(Sub)
Unit C
(Sub)
Unit A
(Main)
Unit B
(Sub)
Summary of Contents for YVAHP0721CW Series
Page 2: ......
Page 10: ...viii SM 16007 ...
Page 14: ......
Page 15: ...SM 16007 1 1 INSTALLATION 1 Installation ...
Page 163: ...SM 16007 2 1 OPERATION 2 Operation ...
Page 164: ...2 2 SM 16007 OPERATION Ɣ 5HIHU WR WKH 6HUYLFH 0DQXDO IRU QGRRU 8QLW RU RQWUROOHU ...
Page 165: ...SM 16007 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 284: ......
Page 285: ...SM 16007 4 1 MAINTENANCE 4 Maintenance ...
Page 360: ......
Page 390: ......
Page 391: ...SM 16007 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 400: ...6 10 SM 16007 FIELD WORK INSTRUCTIONS 0ROOLHU KDUW IRU 5 ft 3 l b ...
Page 401: ...SERVICE PARTS LIST SM 16007 7 1 7 Service Parts List ...
Page 416: ... 2016 Johnson Controls Inc SM 16007 Code No LIT 12012400 Issued November 2016 ...