1-12
SM-16007
INSTALLATION
inch (mm)
Diameter
(D)
Min. Insertion Depth
(B)
Gap
(A - D)
3/16 < D < 5/16
1/4 (6)
0.002 - 0.014
(0.05 - 0.35)
(5 < D < 8)
5/16 < D < 15/32
9/32 (7)
(8 < D < 12)
15/32 < D < 5/8
5/16 (8)
0.002 - 0.018
(0.05 - 0.45)
(12 < D < 16)
5/8 < D < 31/32
13/32 (10)
(16 < D < 25)
31/32 < D < 1-3/8
15/32 (12)
0.002 - 0.022
(0.05 - 0.55)
(25 < D < 35)
1-3/8 < D < 1-25/32
9/16 (14)
(35 < D < 45)
x
Processing at Brazing Connection
To prevent gas leakage at the brazing connection, refer to the table for the insertion depth and the gap for
joint pipe.
B
D
A