SM-16007
1-29
INSTALLATION
[ Example for Pipe Support ]
[ Secure for Liquid Piping, Gas Piping ]
Outdoor Unit
Indoor Unit
Multi-Kit
Install Horizontally
Installing Parts for Piping: Install at Appropriate Intervals
Treatment for Section
of Fire Prevention
Due to changing refrigerant temperatures,
gas and liquid piping will stretch.
Do not fasten gas and liquid piping together with tape.
Distortion and deformation of the piping can occur.
NOTE:
Gas Piping
Installing Part for Piping
Liquid Piping
NOTICE:
When assembling piping onsite with hidden elbow or socket joints, provide a service access doorway to
facilitate close-up examination of interconnecting components.
Ɣ &DXWLRQIRU,QVWDOOLQJDQG6HFXULQJ3LSLQJ
Table 6.1 Piping Size of Outdoor Unit
inch (mm)
Outdoor Unit Capacity
(MBH)
Gas
Liquid
72, 96
7/8 (22.2)
3/8 (9.52)
144 - 192
1-1/8 (28.58)
5/8 (15.88)
288
1-3/8 (34.93)
3/4 (19.05)
Table 6.2 Piping Size of Indoor Unit
inch (mm)
Indoor Unit Capacity
(MBH)
Gas
Liquid
6 - 15
1/2 (12.7)
1/4 (6.35)
18 - 48
5/8 (15.88)
3/8 (9.52)
72
3/4 (19.05)
3/8 (9.52)
96
7/8 (22.2)
3/8 (9.52)
Summary of Contents for YVAHP0721CW Series
Page 2: ......
Page 10: ...viii SM 16007 ...
Page 14: ......
Page 15: ...SM 16007 1 1 INSTALLATION 1 Installation ...
Page 163: ...SM 16007 2 1 OPERATION 2 Operation ...
Page 164: ...2 2 SM 16007 OPERATION Ɣ 5HIHU WR WKH 6HUYLFH 0DQXDO IRU QGRRU 8QLW RU RQWUROOHU ...
Page 165: ...SM 16007 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 284: ......
Page 285: ...SM 16007 4 1 MAINTENANCE 4 Maintenance ...
Page 360: ......
Page 390: ......
Page 391: ...SM 16007 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 400: ...6 10 SM 16007 FIELD WORK INSTRUCTIONS 0ROOLHU KDUW IRU 5 ft 3 l b ...
Page 401: ...SERVICE PARTS LIST SM 16007 7 1 7 Service Parts List ...
Page 416: ... 2016 Johnson Controls Inc SM 16007 Code No LIT 12012400 Issued November 2016 ...