MAINTENANCE
4.1.12 Removing Compressor
Recover the refrigerant using standard EPA procedures and external equipment.
In other instances, recover the refrigerant before starting the work, and turn OFF the power source of the
unit.
NOTE:
'R127WRXFKWKHFRPSUHVVRURUWKHKLJKSUHVVXUHUHIULJHUDQWSLSLQJGXULQJRSHUDWLRQRUZKHQLPPHGLDWHO\
stopping the unit because of the high temperature.
When removing the wiring or reassembling the compressor, be aware not to let the wiring come in contact
with the compressor or the refrigerant piping.
(1) Remove the front service cover according to Section 4.1.1 “Removing Front Service Cover”.
If the outdoor unit is installed close to the wall, remove the refrigerant piping and move the outdoor unit
away from the wall.
(2) Release the tack for the soundproof cover of the compressor and remove the soundproof cover.
(3) Remove the Td thermistor on top of the compressor.
NOTE:
The thermistor holder, thermistor securing plate, and the RC cover are used again when reassembling.
Keep them in a container so that the parts are stored correctly.
TURN OFF all power source switches.
Tool
Long-nose Pliers
Soundproof Cover
RC Cover
Tack
Bind Lace
Waterproof Rubber Cap
for Td Thermistor
Thermistor
Holder
Holder
Td
Thermistor
Thermistor
Securing Plate
NOTE:
When removing the compressor, the electrical box located above the compressor may be disturbed
when removing the RC cover. So the electrical box should be removed before starting work.
If not, the inner aluminum sheet may be damaged when removing the RC cover.
Summary of Contents for YVAHP0721CW Series
Page 2: ......
Page 10: ...viii SM 16007 ...
Page 14: ......
Page 15: ...SM 16007 1 1 INSTALLATION 1 Installation ...
Page 163: ...SM 16007 2 1 OPERATION 2 Operation ...
Page 164: ...2 2 SM 16007 OPERATION Ɣ 5HIHU WR WKH 6HUYLFH 0DQXDO IRU QGRRU 8QLW RU RQWUROOHU ...
Page 165: ...SM 16007 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 284: ......
Page 285: ...SM 16007 4 1 MAINTENANCE 4 Maintenance ...
Page 360: ......
Page 390: ......
Page 391: ...SM 16007 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 400: ...6 10 SM 16007 FIELD WORK INSTRUCTIONS 0ROOLHU KDUW IRU 5 ft 3 l b ...
Page 401: ...SERVICE PARTS LIST SM 16007 7 1 7 Service Parts List ...
Page 416: ... 2016 Johnson Controls Inc SM 16007 Code No LIT 12012400 Issued November 2016 ...