6.4 Piping Size between Outdoor Units
inch (mm)
Model Type
72
96
Piping Size
a
Gas
7/8 (22.2)
7/8 (22.2)
Liquid
3/8 (9.52)
3/8 (9.52)
(Indoor Unit on Left Side)
(Indoor Unit on Right Side)
inch (mm)
Model Type
144
168
192
Combination Unit
Outdoor Unit A
72
96
96
Outdoor Unit B
72
72
96
Piping Connection Kit
MC-NP20A1
Piping Size
a
Gas
1-1/8 (28.58)
1-1/8 (28.58)
1-1/8 (28.58)
Liquid
5/8 (15.88)
5/8 (15.88)
5/8 (15.88)
b
Gas
7/8 (22.2)
7/8 (22.2)
7/8 (22.2)
Liquid
3/8 (9.52)
3/8 (9.52)
3/8 (9.52)
c
Gas
7/8 (22.2)
7/8 (22.2)
7/8 (22.2)
Liquid
3/8 (9.52)
3/8 (9.52)
3/8 (9.52)
* Install the outdoor unit and piping connections in accordance to whatever is applicable to your situation.
Refer to the table for the outdoor unit model, the piping connection kit model, and the piping diameter.
Base Unit
Two Units Combination
To Indoor Units
a
Outdoor Unit
Refrigerant Piping
To Indoor Units
Piping Connection Kit
a
b
c
Outdoor Unit A
Outdoor Unit B
To Indoor Units
Piping Connection Kit
a
b
c
Outdoor Unit B
Outdoor Unit A
Summary of Contents for YVAHP0721CW Series
Page 2: ......
Page 10: ...viii SM 16007 ...
Page 14: ......
Page 15: ...SM 16007 1 1 INSTALLATION 1 Installation ...
Page 163: ...SM 16007 2 1 OPERATION 2 Operation ...
Page 164: ...2 2 SM 16007 OPERATION Ɣ 5HIHU WR WKH 6HUYLFH 0DQXDO IRU QGRRU 8QLW RU RQWUROOHU ...
Page 165: ...SM 16007 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 284: ......
Page 285: ...SM 16007 4 1 MAINTENANCE 4 Maintenance ...
Page 360: ......
Page 390: ......
Page 391: ...SM 16007 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 400: ...6 10 SM 16007 FIELD WORK INSTRUCTIONS 0ROOLHU KDUW IRU 5 ft 3 l b ...
Page 401: ...SERVICE PARTS LIST SM 16007 7 1 7 Service Parts List ...
Page 416: ... 2016 Johnson Controls Inc SM 16007 Code No LIT 12012400 Issued November 2016 ...