3-32
SM-16007
TROUBLESHOOTING
Cancellation of Enforced Thermo-OFF
Press PSW5 for more than three seconds.
This function may damage compressor.
Use this function only in unavoidable condition.
NOTE:
Even if stoppage Alarm “02” is not
always indicated.
Code
Cause
Code
Cause
0
Operation OFF, Power OFF
16
Retry due to Decrease of
Discharge Gas Superheat
1
Thermo-OFF,
Activation of Float Switch
2
Alarm
17
Retry due to Inverter Tripping
3
Freeze Protection,
Overheating Protection
18
Retry due to Voltage Decrease,
Other Retry of Inverter
5
Instantaneous Power Failure
at Outdoor Unit/Reset
19
Expansion Valve Opening
Change Protection
6
Instantaneous Power Failure
at Indoor Unit/Reset
21
Enforced Thermo-OFF
22
Enforced Thermo-OFF
(Hot Start Control at
Crankcase Heater Preheating)
Refer to Cancellation Method
7
Stoppage of Cooling Operation
due to Low Outdoor Air Temp.
Stoppage of Heating Operation
due to High Outdoor Air Temp.
26
Retry due to High Pressure
Decrease
9
Stoppage of Reversing
Valve Switching Control
28
Stoppage due to Outlet Temp.
Decrease in Cooling
10
Demand Enforced Stoppage
11
Retry due to Pressure Ratio
Decrease
30
Stoppage of Thermo-OFF due
to Compressor Excepting
12
Retry due to Low Pressure
Increase
32
Retry due to Abnormal
Transmission of Outdoor Unit
13
Retry due to High Pressure
Increase
36
Retry after Defrosting Operation
14
Retry due to Abnormal Current
of Constant Speed Compressor
39
Stoppage of Thermo-OFF due
to Energy Saving Control
15
Retry due to Vacuum
Abnormality, Discharge Gas
Temp. Increase
Code
Cause
1
Driver IC Error Signal Detection
2
Instantaneous Overcurrent
3
Fin Temp. Increase
4
Electronic Thermal Activation
(Inverter Overcurrent)
5
Voltage Decrease
6
Voltage Increase
7
Abnormal INV. Transmission
8
Abnormal Current Sensor
9
Instantaneous Power Failure
Detection
11
Micro Computer Reset
12
Ground Fault Detecting
13
Abnormal Power Source Phase
16
Inverter Retry
17
Abnormal Control
21
Abnormal Fan Motor (Step-out)
22
Abnormal Setting of PCB
Code
Cause
1
Driver IC Error Signal Detection
2
Instantaneous Overcurrent
3
Fin Temp. Increase
4
Electronic Thermal Activation
5
Voltage Decrease
6
Voltage Increase
7
Abnormal INV. Transmission
8
Abnormal Current Sensor
9
Instantaneous Power Failure
Detection
11
Micro Computer Reset
12
Ground Fault Detecting
15
Reverse Driving
16
Inoperative Fan Motor Detection
17
Abnormal Control
21
Abnormal Fan Motor (Step-out)
(C) Cause of Indoor Unit Stoppage
(D) Cause of Inverter Stoppage
(E) Cause of Fan Controller Stoppage
* Thermo-ON: The outdoor unit and some indoor units are running.
* Thermo-OFF: The outdoor unit and some indoor units stay on, but don’t run.
Summary of Contents for YVAHP0721CW Series
Page 2: ......
Page 10: ...viii SM 16007 ...
Page 14: ......
Page 15: ...SM 16007 1 1 INSTALLATION 1 Installation ...
Page 163: ...SM 16007 2 1 OPERATION 2 Operation ...
Page 164: ...2 2 SM 16007 OPERATION Ɣ 5HIHU WR WKH 6HUYLFH 0DQXDO IRU QGRRU 8QLW RU RQWUROOHU ...
Page 165: ...SM 16007 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 284: ......
Page 285: ...SM 16007 4 1 MAINTENANCE 4 Maintenance ...
Page 360: ......
Page 390: ......
Page 391: ...SM 16007 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 400: ...6 10 SM 16007 FIELD WORK INSTRUCTIONS 0ROOLHU KDUW IRU 5 ft 3 l b ...
Page 401: ...SERVICE PARTS LIST SM 16007 7 1 7 Service Parts List ...
Page 416: ... 2016 Johnson Controls Inc SM 16007 Code No LIT 12012400 Issued November 2016 ...