TROUBLESHOOTING
Cause
Check Item
Action
(Turn OFF Main Switch)
Event
Check for continuity
after temperature of
outdoor fan motor
decreases.
Faulty
Internal
Thermostat
Replace outdoor fan
motor.
Failure
Measure resistance
with a tester.
Tighten or replace
connector.
Contact
Failure
Check connection.
Connect it correctly.
Incorrect
Connection
Excessively
Low Suction
Pressure
(in Vacuum)
Internal
Thermostat for
Outdoor Fan
is Activated
in Heating
Operation
Measure coil resistance
and insulation resistance.
Replace outdoor fan
motor if faulty.
Faulty Outdoor Fan Motor
Check charged ref.
volume or check for
leakage.
Repair leakage and
correctly charge ref.
Shortage of Refrigerant
Check electrical
system and ref. cycle.
Correctly connect
indoor unit and
outdoor unit.
Incorrect Connection
between Indoor Unit and
Outdoor Unit
Check connector
for O.U. PCB.
Replace pressure
sensor if faulty.
Abnormal Low or High
Pressure Sensor
Check stop valve.
Open stop valve.
Closed Stop Valve
Check Td thermistors
for compressors and
measure Td thermistor
resistance.
Repair or replace
Td thermistor.
Expansion Valve Closed by
Disconnecting Td Thermistor
Check connector for
O.U. PCB.
Repair connector for O.U.
PCB or expansion valve.
Replace it if faulty.
Locked Expansion Valve
(Fully Closed)
Summary of Contents for YVAHP0721CW Series
Page 2: ......
Page 10: ...viii SM 16007 ...
Page 14: ......
Page 15: ...SM 16007 1 1 INSTALLATION 1 Installation ...
Page 163: ...SM 16007 2 1 OPERATION 2 Operation ...
Page 164: ...2 2 SM 16007 OPERATION Ɣ 5HIHU WR WKH 6HUYLFH 0DQXDO IRU QGRRU 8QLW RU RQWUROOHU ...
Page 165: ...SM 16007 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 284: ......
Page 285: ...SM 16007 4 1 MAINTENANCE 4 Maintenance ...
Page 360: ......
Page 390: ......
Page 391: ...SM 16007 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 400: ...6 10 SM 16007 FIELD WORK INSTRUCTIONS 0ROOLHU KDUW IRU 5 ft 3 l b ...
Page 401: ...SERVICE PARTS LIST SM 16007 7 1 7 Service Parts List ...
Page 416: ... 2016 Johnson Controls Inc SM 16007 Code No LIT 12012400 Issued November 2016 ...