3-114
SM-16007
TROUBLESHOOTING
3.4.2 Test Run from Outdoor Unit Side
The procedures for the test run from the outdoor unit side are indicated below. Setting of this DIP switch is
possible with the power source ON.
O
Do not touch any other electrical part when operating switches on the PCB.
O
Do not attach or detach the service cover when the power source for the outdoor unit is supplied
and the outdoor unit is operated.
O
Turn all the DIP switches of DSW4 OFF when the test run operation is completed.
DIP Switch Setting
Operation
Remarks
Test Run
1. Setting of Operation Mode
Cooling: Set DSW4-2 OFF.
Heating: Set DSW4-2 ON.
2. Starting Test Run
Set DSW4-1 ON and the operation is
started after a few to 20 seconds.
1. The indoor unit automatically
starts operating when the test run
of the outdoor unit is set.
2. The ON/OFF operation can
be performed from the wired
controller or DSW4-1 of the
outdoor unit.
3. The operation continues for
two hours without Thermo-OFF.
* Note that the indoor units operate in
conjunction with the test run operation
of the outdoor unit.
* If the test run is started from the
outdoor unit and stopped from the wired
controller, the test run function of the
wired controller is cancelled. However,
the test run function of the outdoor unit
is not cancelled. Check to ensure that
the DSW4-1 of the outdoor unit PCB is
turned OFF.
* If multiple indoor units are connected
with one wired controller, perform the
test run operation individually for each
refrigerant system one by one. Then,
make sure to turn the power source
OFF for the indoor units in other
refrigerant systems not included in the
test run.
* The setting of DSW4 is not required for
the test run from the wired controller.
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2 3 4 5 6
If heating operation leave
DSW4-2 at ON.
Outdoor Unit
Test Run
Power OFF.
Indoor
Unit
DSW4
Switch for Setting of Service Operation and Function
1. Test Run
2. COOL/HEAT Setting
(ON: Heating Operation)
3. OFF (Fixed)
4. Manual Compressor OFF
5. OFF (Fixed)
6. OFF (Fixed)
ON
OFF
1 2 3 4 5 6
Setting of DIP Switch (Factory Setting)
NOTE:
Thermo-ON: The outdoor unit and some indoor units are running.
Thermo-OFF: The outdoor unit and some indoor units stay on, but don't run.
Summary of Contents for YVAHP0721CW Series
Page 2: ......
Page 10: ...viii SM 16007 ...
Page 14: ......
Page 15: ...SM 16007 1 1 INSTALLATION 1 Installation ...
Page 163: ...SM 16007 2 1 OPERATION 2 Operation ...
Page 164: ...2 2 SM 16007 OPERATION Ɣ 5HIHU WR WKH 6HUYLFH 0DQXDO IRU QGRRU 8QLW RU RQWUROOHU ...
Page 165: ...SM 16007 3 1 TROUBLESHOOTING 3 Troubleshooting ...
Page 284: ......
Page 285: ...SM 16007 4 1 MAINTENANCE 4 Maintenance ...
Page 360: ......
Page 390: ......
Page 391: ...SM 16007 6 1 FIELD WORK INSTRUCTIONS 6 Field Work Instructions ...
Page 400: ...6 10 SM 16007 FIELD WORK INSTRUCTIONS 0ROOLHU KDUW IRU 5 ft 3 l b ...
Page 401: ...SERVICE PARTS LIST SM 16007 7 1 7 Service Parts List ...
Page 416: ... 2016 Johnson Controls Inc SM 16007 Code No LIT 12012400 Issued November 2016 ...