3-42
SM-16007
TROUBLESHOOTING
Cause
Check Item
Action
(Turn OFF Main Switch)
Event
Activation of
High Pressure
Switch due to
Excessively
High Discharge
Pressure
Clogging of Heat
Exchanger?
Remove clogging.
Check for dust on
air filter.
Remove dust.
Check for any obstacles
at inlet or outlet of
heat exchanger.
Remove obstacles.
Check service space
is sufficient.
Secure sufficient
service space.
Check fan motor speed.
Outdoor Fan: Cooling
Indoor Fan: Heating
Replace fan motor
if faulty.
Insufficient Airflow to
Heat Exchanger
(Outdoor Heat Exchanger
during Cooling Operation
or Indoor Heat Exchanger
during Heating Operation)