Section 6: Programming
017 – 24-Hour Burglary
This zone type is active at all times. It reports an alarm if the alarm system is armed or disarmed. This zone type sounds the siren for
the length of Bell time-out if the audible attribute is enabled.
018 – 24-Hour Bell/Buzzer
When the alarm system is armed and this type of zone is tripped, the siren activates for the duration of the bell time-out. If the alarm
system is disarmed when this type of zone is tripped, the keypad buzzer activates until an access code is entered.
023 – 24-Hour Supervisory
This zone is active and reports alarms at all times when tripped. The siren and keypad buzzer do not activate.
Note:
The supervision options (NC, SEOL, DEOL, TEOL) do not affect the functionality of this zone. The restored state of this zone
type is 5.6k, the alarm state is short and the trouble state is open. For use with normally open contacts.
024 – 24-Hour Supervisory Buzzer
When tripped, the keypad buzzer emits a steady tone until a valid access code is entered.
025 – Auto Verify Fire
Hardwired smoke detectors
When the zone is activated, a 30-second delay begins but no fire alarm sounds. If the same zone is activated again up to 60 seconds
after the delay expires, the alarm is triggered immediately. If the same zone is activated after 60 seconds, the entire sequence begins
again.
If a second fire zone is violated during the auto-verify sequence, both zones a fire alarm is immediately triggered.
Wireless smoke detectors
When the zone is activated, a 40-second delay begins. The alarm is triggered if the zone is still faulted after 30 seconds. If the zone is
no longer in alarm, an 80-second verification timer begins. If any fire zone is activated during this period, the alarm is triggered.
If another fire zone is activated during the auto verify sequence, both zones go into alarm immediately.
Note:
Wireless smoke detectors used with this zone type must have a built in siren to act as a pre-alert to the system alarm.
Note:
The supervision options (NC, SEOL, DEOL, TEOL) do not affect the functionality of this zone. The restored state of this zone
type is 5.6kΩ, the alarm state is short and the trouble state is open.
027 – Fire Supervisory
When this zone is tripped, the keypad buzzer activates and a supervisory alarm is sent to the monitoring station. A valid access code
must be entered to silence the buzzer.
Note:
The supervision options (NC, SEOL, DEOL, TEOL) do not affect the functionality of this zone. The restored state of this zone
type is 5.6k, the alarm state is short and the trouble state is open.
040 – 24-Hour Gas
Instant alarm when activated, audible alarm at default. This zone type may be assigned to any device type.
041 – 24-Hour CO
This zone type is used with CO detectors. In the event of an alarm, a distinctive siren cadence is sounded. This is followed by a 5-
second pause and then repeated. After 4 minutes, the 5-second pause is extended to 60 seconds; however, BTO must be
programmed with a value of 5 minutes or higher. The siren is silenced when an access code is entered or the siren times out.
Note:
The supervision options (NC, SEOL, DEOL, TEOL) do not affect the functionality of this zone. The restored state of this zone
type is 5k6, the alarm state is short and the trouble state is open. For use with normally open contacts.
042 – 24-Hour Holdup
Instant alarm when activated, silent alarm at default.
Note:
Not for use in UL listed installations.
043 – 24-Hour Panic
Instant alarm when activated, audible alarm at default.
045 – 24-Hour Heat
Instant alarm when activated, audible alarm at default.
046 – 24-Hour Medical
Instant alarm when activated, audible alarm at default.
- 89 -